Solar, Titan 130, 2014, 15.2MW, 11kV, 50Hz, Gas Turbine Generator Package

Description

  1. Overview
    1. Year of manufacture: 2013/14
    2. Condition: As new
    3. Operating hours: 0
    4. Status: Installed
    5. Fuel: NG or syngas
  2. Gas Turbine
    1. Manufacturer: Solar
    2. Model: T130
    3. Variant: 20501 GSC
    4. Rated output: 15.2 MW (natural gas) / 17 MW (syngas)
    5. Combustion: Standard
  3. Gear
    1. Manufacturer: Solar Turbines Incorporated
    2. Year: 2014
    3. Type: Epicyclic
    4. Ratio: 7.4648: 1
    5. Rated power: 26,251 hp
    6. Input speed: 11,197 rpm
    7. Output speed: 1,500 rpm
    8. Overload factor: 1.1
  4. Generator
    1. Manufacturer: ABB
    2. Model: AM130 1000LM
    3. Rated output: 22,789 kVA
    4. Power factor: 0.8
    5. Voltage: 11 kV
    6. Frequency: 50 Hz
  5. Scope of Supply
    1. Solar Titan T130 gas turbine generator (skid mounted)
    2. ABB generator AM130 1000LM (skid mounted)
    3. Donaldson air intake system
    4. Combustion train fuel control and isolation skids
    5. Non-core GTG equipment (e.g., external oil cooler, oil/mist eliminators, firefighting system, etc.)
  6. Excluded Items
    1. HRSGs and stacks
  7. Gas Turbine Generator Details
    1. Solar Titan 130 GTG is designed to produce approximately 17 MW of electricity based on syngas and 15.2 MW of electricity based on natural gas.
    2. The GTG is designed to run on either fuel continuously.
    3. The GTG is controlled via the local Solar supplied PLC, including all safety related functionality.
    4. The basic process control system (BPCS) communicates with the Solar PLC, feeding set points to and receiving alarms from the Solar PLC.
    5. The GTG was installed in circa 2013/14, but not commissioned.
    6. It has been preserved in accordance with manufacturer recommendations.
    7. The GTG is designed to take a significantly wider range of fuel stocks than a typical Solar Titan GTG.
    8. In addition to natural gas, the system is designed to operate with much poorer quality fuel (syngas) by utilising additional fuel manifolds.
  8. Air Intake System
    1. The Donaldson TTD air inlet system is designed to provide self-cleaning, anti-icing, single stage, high efficiency filtration for prolonged periods (up to two years) in harsh climates without turbine shutdown for filter cleaning or replacement.
    2. It utilizes cylindrical filter elements, hung vertically from a horizontal tubesheet.
    3. These filters are cleaned by pulsing a wave of air into them opposite the normal air flow direction.
  9. Generator Details
    1. The gas turbine uses an ABB type AMS 1000LM generator to produce its electrical power.