General Electric, 127 MW, 2003, 50Hz, Gas Turbine Power Plant

Description

  1. Unit 1 - Gtg 1A
    1. Overview
      1. Plant: Unit 1
      2. Name of the unit: GTG 1A
      3. Installed capacity: 42.3 MW
      4. Average production per year (last 3 years): 1,866,834,218 MWh
      5. Type: Gas turbine (GT)
      6. Number of groups: 1
      7. Year of commissioning: 2005
      8. Estimated total useful lifetime: 22 years
    2. Land
      1. In ownership: Yes
      2. Size total: 51,078 m²
      3. Size of production area: 9,333 m²
      4. Size of arable land / other area: 41,745 m²
    3. Buildings
      1. Number of buildings: 6
      2. In ownership: Yes
      3. Size total: 10,353 m²
      4. Size of office area: 939 m²
      5. Size of workshop area: 81 m²
      6. Size of production area: 9,333 m²
      7. General condition: Good
    4. Power Plant Design
      1. Year of production: 2003
      2. Manufacturer of the main unit: General Electric
      3. Contractor: General Electric
      4. Engineering department: General Electric
      5. Turnkey project: No
    5. Plant Occupancy
      1. Net plant output: 40 MW
      2. Equivalent operating hours 2012: 5,925
      3. Equivalent operating hours 2011: 6,296
      4. Equivalent operating hours 2010: 6,082
      5. Equivalent operating hours 2009: 7,208
      6. Equivalent operating hours 2008: 7,380
      7. Equivalent operating hours 2007: 7,730
      8. Equivalent operating hours 2006: 7,016
      9. Total operating hours since commissioning: 47,637.00 h
      10. Number of starts 2012: 166
      11. Number of starts 2011: 166
      12. Number of starts 2010: 237
      13. Number of starts 2009: 25
      14. Number of starts 2008: 25
      15. Number of starts 2007: 16
      16. Number of starts 2006: 63
      17. Total starts since commissioning: 698.00
      18. Maintenance cycle by: Hours
      19. Small maintenance cycle: 12,000-CI
      20. Large maintenance cycle: 24,000-HGPI
      21. Overhaul cycle - major maintenance: 48,000-MI
      22. Electrical frequency: 50 Hz
      23. Actual condition of the unit: Good
    6. Storage of Combustible
      1. Size of storage: No
    7. Gas Turbine
      1. Year of construction: 2003
      2. Manufacturer: GE
      3. Model: P G 6 5 9 1 C
      4. Type: Frame 6 C
      5. Production: 42.3 MWe
      6. Pressure ratio: 1/16.4
      7. Flow rate: 110 lb./sec
      8. Turbine speed: 7,100 rpm
      9. Exhaust gas temperature: 600 °C
      10. Dry low NOx combustor: Yes
      11. Air quench cooler: No
      12. Specific consumption: 310 Sm³/MWh
      13. Water injected: No
      14. Dry: No
      15. Distillate fuel: Yes
      16. One axle / two axles: 2
      17. Dual fuel combustion: Yes
      18. Fast start capacity: No
    8. Hrsg
      1. Year of construction: 2004
      2. Manufacturer: NEM
      3. Model: HRSG
      4. Type: Horizontal
      5. Gas temperature entry: 598 °C
      6. Gas temperature exit: 102 °C
      7. Steam pressure: 58 - 5 kg/cm²
      8. Height of chimney or stack: 29 m
      9. Number of pressure levels: 2
      10. Pressure in stages HP, MP, LP: HP: 58 bar, LP: 5 bar
      11. Production of steam: 65 t/h
      12. Actual condition: Good
    9. Generator
      1. Manufacturer: VATEC-ELIN
      2. Model: Outdoor
      3. Type: 2 poles, 3 phase, wye connection, 50 Hz
      4. Cooling system: Air
      5. Rating: 39 MW
      6. Voltage: 11.5 kV
      7. Power factor: 0.8
      8. Output: 39 MVAr
      9. Year of construction: 2003
      10. Year of last extensive inspection or reconstruction: 2008
    10. Transformer
      1. Manufacturer: ABB
      2. Model: 1ZTR231900
      3. Type / voltage level: 1ZTR231900 high/low
      4. Load: 54 MVA
      5. Year of construction: 2004
      6. Transformation ratio: 154/11.5
    11. Cooling System
      1. Fluid cooling: Yes
      2. Cooling tower: No
      3. Manufacturer: GEA
      4. Type: Fin fan cooler
      5. Height: 3,967 m
      6. Material: Steel
      7. Number of cooling cells: 8
      8. Diameter of vents: 1.25 m
      9. Fan speed: 705 rpm
      10. Herbicide for biological pollution: No
      11. Year of construction: 2005
      12. Year of last extensive inspection or reconstruction: 2008
      13. Expected remaining useful lifetime: 18 years
      14. Actual condition: Good
  2. Unit 2 - Gtg 1B
    1. Overview
      1. Plant: Unit 2
      2. Name of the unit: GTG 1B
      3. Installed capacity: 42.3 MW
      4. Average production per year (last 3 years): 1,904,159,963 MWh
      5. Type: Gas turbine (GT)
      6. Number of groups: 2
      7. Year of commissioning: 2005
      8. Estimated total useful lifetime: 22 years
    2. Power Plant Design
      1. Year of production: 2003
      2. Manufacturer of the main unit: General Electric
      3. Contractor: General Electric
      4. Engineering department: General Electric
      5. Turnkey project: No
    3. Plant Occupancy
      1. Net plant output: 40 MW
      2. Equivalent operating hours 2012: 6,434.9
      3. Equivalent operating hours 2011: 6,547.8
      4. Equivalent operating hours 2010: 5,633
      5. Equivalent operating hours 2009: 8,305
      6. Equivalent operating hours 2008: 6,557
      7. Equivalent operating hours 2007: 8,021
      8. Equivalent operating hours 2006: 6,480
      9. Total operating hours since commissioning: 47,978.70 h
      10. Number of starts 2012: 182
      11. Number of starts 2011: 182
      12. Number of starts 2010: 205
      13. Number of starts 2009: 25
      14. Number of starts 2008: 19
      15. Number of starts 2007: 23
      16. Number of starts 2006: 32
      17. Total starts since commissioning: 668.00
      18. Maintenance cycle by: Hours
      19. Small maintenance cycle: 12,000-CI
      20. Large maintenance cycle: 24,000-HGPI
      21. Overhaul cycle - major maintenance: 48,000-MI
      22. Electrical frequency: 50 Hz
      23. Actual condition of the unit: Good
    4. Storage of Combustible
      1. Size of storage: No
    5. Gas Turbine
      1. Year of construction: 2003
      2. Manufacturer: GE
      3. Model: P G 6 5 9 1 C
      4. Type: Frame 6 C
      5. Production: 42.3 MWe
      6. Pressure ratio: 1/16.4
      7. Flow rate: 110 lb./sec
      8. Turbine speed: 7,100 rpm
      9. Exhaust gas temperature: 600 °C
      10. Dry low NOx combustor: Yes
      11. Air quench cooler: No
      12. Specific consumption: 310 Sm³/MWh
      13. Water injected: No
      14. Dry: No
      15. Distillate fuel: Yes
      16. One axle / two axles: 2
      17. Dual fuel combustion: Yes
      18. Fast start capacity: No
    6. Hrsg
      1. Year of construction: 2004
      2. Manufacturer: NEM
      3. Model: HRSG
      4. Type: Horizontal
      5. <