York Shipley, SPH 600, 1973, 600 HP, 250 PSIG, Packaged Firetube Boiler

Description

  1. Overview
    1. York Shipley packaged firetube boiler, model SPH 600
    2. Manufactured in 1973 in accordance with ASME code, section 1, for a design pressure of 250 psig
    3. National board certified #13549
    4. Three (3) pass dryback design
    5. Fully modulating forced draft burner is integrally mounted, piped, and wired on the boiler front for easy setup and maintenance
  2. Specifications
    1. 600 hp, 250 psig, #2 oil and natural gas
    2. Fuels: #2 oil, #4 oil, #5 oil, and natural gas
    3. Firing capability / turndown / modulation: 4:1
    4. Dual fuel burner arrangement: standard burner
    5. Emissions: standard
    6. Primary low water cut-off: McDonnell Miller pump control modulating
    7. Secondary low water cut-off: Warrick probe with manual reset
    8. Water column gauge cocks
    9. Front and rear davited doors
    10. Pressure gauge with isolation valve
    11. Flame safety type: 70 Honeywell
    12. Boiler/burner control center consisting of starters, relays, fuse blocks, limit switches, alarm bell, indicating lights, control circuit transformer, high limit control, and manual/automatic firing rate adjustment
    13. Steam pressure limit switches: operating limit, safety limit with manual reset, and modulating steam pressure controller for running operation and standby operation
    14. Belt driven atomizing air compressor with lube oil tank
    15. IRI insurance approvals
    16. UL listing
  3. Connections
    1. Steam outlet: 8” x 300#
    2. Blowdown: 2.0” NPT
    3. Surface blow-off: 1.5” NPT
    4. #2 oil supply and return: 1.25” NPT
    5. Feedwater: 2.5” NPT
    6. Natural gas: 3.0” NPT
    7. Primary electric: 230V / 3 phase / 60 Hz
    8. Exhaust/vent: 24” ID
  4. Dimensions
    1. Length overall: 26’ 10”
    2. Shell: 23’ 4”
    3. Width overall: 9’ 4”
    4. Shell: 7’ 10”
    5. Height overall: 10’ 9”
    6. Vent: 9’ 7”
    7. Shipping weight: 47,000 lbs
    1. USA