Zurn, VL, 1972, 650-700 HP, 20000 lbs/hr, 200 PSIG

Description

  1. Overview
    1. Unused 20,000#/hr. Zurn 'VL' package watertube boiler
    2. 200 psig dp
    3. VL design provides wide flexibility for firing a variety of fuels and is suitable for hogged fuels such as wood, sawdust, bark, bagasse
    4. Unit is described per the attached data sheet
  2. Specifications
    1. Used 20,000#/hr. Cleaver Brooks, 260 psig dp, package watertube boilers, model D-42
    2. 2-drum bent tube type, referred to as a "D" design
    3. Composed of a 36" id steam drum and a 24" od lower drum with 2" od tubes
    4. Each boiler has a total heating surface of 1,933 sq. ft., of which 360 sq. ft. are in the waterwalls
    5. Built in 1972 in accordance with ASME code and bearing N.B. and H.S.B. stampings
    6. Approximate dimensions: 19'-2" L x 10'-8" W x 12'-10" H
    7. Approximate shipping weight: 46,000 lbs.
  3. Burner And Controls
    1. Cleaver-Brooks, model WT293X-BRI combination forced draft burner for gas and #2 oil firing
    2. Forced draft fan with a 25 hp motor, 3/60/460V
    3. Fully automatic electric positioning combustion control panel with flame safeguard and programming control system
    4. Includes all integrally piped and wired components such as control panel, fuel trains, actuators, heater, piping and trim
    5. Control voltage is 1/60/110V
    6. Valve trim consists of feedwater stop and check valves, safety valves, as well as miscellaneous valve trim and regulators
  4. Included
    1. Coen burner for #2 oil and low 100 btu value gas
    2. Burner can be left on the boiler, and a stoker placed underneath
  5. Quantity
    1. 2 units available