Cleaver Brooks, CBLE200-800, 2001, 800 HP, 200 PSI, Packaged Firetube Boiler

Description

  1. Overview
    1. Powerhouse model CBLE200-800 packaged firetube boiler
    2. Unit number B-521
    3. Built in 2001
    4. Fully reconditioned and shop tested 800 hp Cleaver Brooks packaged firetube boiler
    5. 200 psig asme design pressure
    6. Shop conversion prior shipment to fire #6 oil
    7. Complete with trim and controls as outlined in the attached spec sheet
  2. Specifications
    1. 800 hp, 200 psi, #2 oil and natural gas
    2. Cleaver Brooks 800 hp packaged firetube boiler, model CBLE200-800, constructed in 2001 in accordance with the asme code for a design pressure of 200 psig
    3. Four-pass dryback design with 3500 square feet of fireside heating surface
    4. Shell insulated with two inches of compressed fiberglass and covered with a heavy gauge sheet steel casing
    5. Fully modulating forced draft burner integrally mounted, piped and wired on the boiler front allowing for ease of flame observation, set-up and maintenance
  3. Valve Trim, Controls And Auxiliary Equipment
    1. Low nox burner with integral flue gas recirculation assembly for 30 ppm nox emissions
    2. Primary low water cut-off, mcd&m no. 194a-7b
    3. Secondary low water cut-off, warrick probe type, #c-2 with manual reset
    4. Boiler valve trim; feedwater stop and check valves, blowdown and blow-off valves, vent valve and safety valves per asme code
    5. Water column with sight glass, gauge cocks, tricocks and blowdown valves
    6. Front and rear hinged covers
    7. Pressure gauge with isolation valve and stack thermometer
    8. Nema 4 electrical entrance box and control panel
    9. Boiler/burner control center consisting of a fireye e-110 primary flame control and detector, motor starters, relays, fuse blocks, limit switches, alarm bell, indicating lights, control circuit transformer, elapsed time meter, low fire hold control and potentiometer with selector switch for manual or automatic firing rate adjustment
    10. Operating steam pressure limit switch, safety steam pressure limit switch with manual reset, low fire hold control and modulating steam pressure control
    11. Rigid and seal-tite conduit and wiring
    12. Atomizing air compressor with lube oil tank and cooler
    13. Fuel pump and motor drive with relief valve, strainer and starter, shipped loose
    14. Nfpa-8501, iri and fm approvals, u.l. labeling
  4. Connections
    1. Steam - 8" x 300#
    2. Nat. gas - 3.0" npt
    3. Blowdown - 2.0" npt
    4. Exhaust - 24" id
    5. Feedwater - 2.0" npt
    6. #2 oil, s&r- 0.75" npt
    7. Blow-off - 1.0" npt
    8. Electric - 460v/3ph/60cy
  5. Dimensions And Weight
    1. 26' 07" l x 10' 03" w x 11' 02" h
    2. 57,000 lbs – shipping, 80,000 lbs – operating