Hurst, SE4-GA2-600-200, 600 BHP Boiler System, 200 PSI, with Webster Gas/#2 Oil Burner and Feed System

Description

  1. Overview
    1. Hurst boiler system
    2. Series model: SE4-GA2-600-200
    3. Capacity: 600 bhp boiler system
    4. Steel firetube, three pass, wetback, boiler-burner unit - 25,200 mbh input - 20,085 mbh output - 20,700 lbs./hr. - 600 bhp
  2. Specifications
    1. 200 psi asme code design
    2. 200 psi relief valve
    3. Operating and limit controls
    4. Firing rate controller
    5. 1" feedwater stop and check valves
    6. 1" surface blowdown valve
    7. Surface skimmer tube
    8. Mm 194-7b primary lwco/controller
    9. Elect. modulating feedwater valve
    10. 3-valve by-pass on feedwater valve
    11. M&m #750 secondary lwco (mr)
    12. (1) 1.5" quick opening blowdown valve
    13. (1) 1.5" slow opening blowdown valve
    14. Stack thermometer
    15. Steam pressure gauge w/ iso. valve
    16. Sample cooler
  3. Burner
    1. Webster gas/#2 oil burner
    2. Burner mounted control panel
    3. Indicating lights and switches
    4. Manual potentiometer
    5. Honeywell rm7800 series fsg control
    6. Uv flame sensor
    7. Pre and post purge
    8. Full modulation firing
    9. Main gas train
    10. Oil train
    11. Pilot gas train
    12. Main and pilot gas regulators (5 psi)
    13. 460/3/60 blower motor
    14. Remote oil pump set
    15. Air compressor set
    16. Ul and fm approval
  4. Feed System
    1. Blr. feed system model: fm-d-600-200 packaged duplex
    2. 600 gallon storage
    3. 48" dia. x 84" long tank
    4. 60" high structural steel stand
    5. 1/4" thick carbon steel tank
    6. Tank drain valve
    7. Tank thermometer
    8. Gauge glass set
    9. Float type make-up water valve
    10. Steam pre-heater assembly w/ prv
    11. 2 cr15-9a vertical multi stage pumps, 15 hp, 208/3/60, tefc motors, 60 gpm @ 206 psig max.
    12. 1 pump for stand-by
    13. Suction piping w/ shut off valve and strainer
    14. Complete nema 1a control panel with motor starters w/ disconnects, circuit breakers, pump transfer switch, indicating lights, control transformer
  5. Blowdown
    1. Model: 14x34 factory packaged blowdown separator
    2. Aftercooler
    3. Temperature regulating valve
    4. Y strainer
    5. Check valve
    6. Thermometer
  6. Options
    1. 4" flg. angle non-return valve
    2. 4" flg. gate valve
    3. Spool piece