Alankar, AWB-60 Gas, Gas Fired Boiler, 6000 kg/hr, 10.54 kg/cm2, 5000x3800x4200mm

Description

  1. Overview
    1. Type: Horizontal smoke tube type, 3 pass package boiler, fully wet back.
    2. Fuel: Gas.
    3. Model: AWB-60 gas.
  2. Specifications
    1. Gas consumption: 240 - 1200 kW, 24 - 120 kg/hr, NCV 8600 kcals/kg.
    2. Capacity: 6000 kg/hr from and at 100 °C.
    3. Working pressure: 10.54 kg/cm² (g).
    4. Fire grate area: 6.40 sq m.
    5. Heating surface: 253 sq m.
    6. Type of draught: Balanced draught.
    7. Maximum flue gas temperature: 200 ± 20 °C.
    8. Boiler feed water quality: Maximum hardness 8 ppm, pH 8.5 to 9.
    9. Thermal efficiency: 77 ± 3%.
  3. Electrical Load
    1. Connected: 60 hp (+22 hp in case of auto firing).
    2. Operating: 40 hp (+22 hp in case of auto firing).
  4. Dimensions and Weight
    1. Overall dimensions: 5000 x 3800 x 4200 mm.
    2. Operating weight: 67,000 kg.
    3. Empty weight: 44,000 kg.