York-Shipley, YS5-800-150ST, 800 HP, 150 PSI, 3-Pass Dryback Boiler (New)

Description

  1. Overview
    1. Heating surface: 5 square feet per boiler hp
    2. Design: High efficiency 3-pass dryback
    3. Capacity: 800 boiler hp
    4. Pressure: 150 psi steam
    5. Maximum output: 27,600 pounds per hour
    6. Gas input (cfh): 33,600 maximum
    7. Electrical: All voltages, 3-phase
  2. Dimensions
    1. Length: 394 inches
    2. Width: 110 inches
    3. Height: 123.75 inches
  3. Burner and Controls
    1. Burner models: Webster JB series
    2. Burner listing: UL and CSD-1
    3. Modulation: Full modulation
    4. Flame control: Honeywell RM7800
    5. Casing: Polished stainless
    6. Primary lwco: MM 157-SRL
    7. Aux lwco: MM RS-1-BR-1
    8. Lwco relya: Warrick 26MB1A0E
  4. Connection Sizes
    1. Steam: 8” 300# flange
    2. Stack: 28” flange
    3. Blowdown/drain: 2” npt
    4. Feedwater: 2.5” npt
    5. Surface blow: 1.5” npt
  5. Lead Time and Options
    1. Lead time: 10 to 16 weeks depending on model and factory load cycling
    2. Optional burner upgrades available: Low nox, parallel positioning and more
    3. Ancillary equipment available: Deaerators, feed systems, blow-down separators and more
    4. Factory-direct from the manufacturer