Description Overview Output: 62.5 MVA Stator current: 2440 A Stator voltage: 10.5 kV Frequency: 50 Hz Speed: 3000 rpm Cooling: hydrogen external cooled Insulation: class B Steam Turbine Model: N50-8.83-1 high pressure Single cylinder Condensing type Rated power: 50 MW Max power: 55 MW (only under certain condition, not for testing) Speed: 3000 rpm Steam inlet pressure: 8.83 MPa Steam inlet temperature: 535 °C Low pressure steam exhaust pressure: 0.0054 MPa (at meter 0.1013 - 0.0054 = 0.0959 MPa) Exhaust temperature at load max: 65 °C Cooling water temperature: normal 20 °C, max 33 °C Cooling water flow: 8160 t/h Water inlet temperature: 220 °C Total 21 stages (1 adjustable + 20 pressure stages) At stages 5, 8, 11, 15, 17, 19 set non-adjustable steam extraction At the 5th stage of the steam turbine bottom there are 2 of Ø168 adjustable heat extraction holes Pressure: 1.4 MPa to 2.69 MPa, temperature: 337.8 to 400.4 °C Total steam consumption rate: 193.032 t/h Steam consumption (guarantee value): 3.72 kg/kWh Heat rate: 9399 kJ/kWh Extraction points and specifications: Back of stage 1: pressure 5.6 MPa, temperature 480 °C Back of stage 5: pressure 2.691 MPa, temperature 390 °C, extraction capacity 12.28 t/h, re-heater output temperature 220.4 °C, re-heater #2 high add Back of stage 8: pressure 1.385 MPa, temperature 312 °C, extraction capacity 6.83 t/h, re-heater output temperature 190 °C, re-heater #1 high add Back of stage 11: pressure 0.772 MPa, temperature 249 °C, extraction capacity 8.21 t/h, re-heater output temperature 158 °C, re-heater de-oxygenator Back of stage 15: pressure 0.293 MPa, temperature 156 °C, extraction capacity 6.36 t/h, re-heater output temperature 130 °C, re-heater #3 low add Back of stage 17: pressure 0.131 MPa, temperature 107 °C, extraction capacity 8.85 t/h, re-heater output temperature 105 °C, re-heater #2 low add Back of stage 19: pressure 0.041 MPa, temperature 76 °C, extraction capacity 6.9 t/h, re-heater output temperature 75 °C, re-heater #1 low add Boiler Boiler type: single steam natural convection coal dust boiler, steel structure, reverse U layout Model: SG-220/9.8-M298 Rated capacity: 220 t/h Saturated steam pressure: 10.78 MPa Overheat steam pressure: 9.8 MPa Steam temperature: 540 °C Boiler efficiency: 91.1% Last major overhaul of power plant was in 2004, 2005, and 2007 Condition Quantity: 3