Olympian, GEP110-4, 110 kVA, 50/60 Hz, Perkins Engine, Sound Attenuated Enclosure

Description

  1. Overview
    1. GEP110-4 generator complete with sound attenuated enclosure, single skin fuel tanks, and power wizard 1.1 control panels.
    2. 400 V, 50 Hz.
  2. Output Ratings
    1. Generating set model prime 100.0 kVA / 80.0 kW and standby 110.0 kVA / 88.0 kW at 380-415 V, 50 Hz.
    2. Generating set model prime 113.0 kVA / 90.4 kW and standby 125.0 kVA / 100.0 kW at 480 V, 60 Hz.
  3. Technical Data
    1. Engine make and model: Perkins 1104C-44TAG2.
    2. Alternator model: LL3014B.
    3. Base frame type: Fbc2 - (08Hr).
    4. Circuit breaker type: 3 pole MCCB.
    5. Frequency: 50 Hz / 60 Hz.
    6. Engine speed: 1500 rpm at 50 Hz, 1800 rpm at 60 Hz.
    7. Fuel tank capacity: 250 litres (66.0 US gal).
    8. Fuel consumption, prime: 21.9 l/hr (5.8 US gal/hr) at 50 Hz, 26.3 l/hr (6.9 US gal/hr) at 60 Hz.
    9. Fuel consumption, standby: 24.1 l/hr (6.4 US gal/hr) at 50 Hz, 29.3 l/hr (7.7 US gal/hr) at 60 Hz.
  4. Engine Technical Data
    1. Manufacturer: Perkins.
    2. Model: 1104C-44TAG2.
    3. Number of cylinders/alignment: 4 / in line.
    4. Cycle: 4 stroke.
    5. Induction: turbocharged air to air charge cooled.
    6. Cooling method: water.
    7. Governing type: electronic.
    8. Governing class: ISO 8528 G2.
    9. Compression ratio: 18.3:1.
    10. Displacement: 4.4 l (268.5 cu).
    11. Bore/stroke: 105.0 mm (4.1) / 127.0 mm (5.0).
    12. Moment of inertia: 1.51 kg m² (5160 lb in²).
    13. Engine electrical system: 12 V negative ground, 65 amp battery charger.
    14. Weight dry: 500 kg (1102 lb); wet: 520 kg (1146 lb).
  5. Lubrication System
    1. Oil filter type: spin-on, full flow.
    2. Total oil capacity: 8.0 l (2.1 US gal).
    3. Oil pan capacity: 7.0 l (1.8 US gal).
    4. Oil type: API CC/SE.
    5. Cooling method: water.
  6. Performance 50 Hz / 60 Hz
    1. Engine speed: 1500 rpm at 50 Hz, 1800 rpm at 60 Hz.
    2. Gross engine power standby: 103.0 kW (138.0 hp) at 50 Hz, 117.5 kW (158.0 hp) at 60 Hz.
    3. Gross engine power prime: 93.6 kW (126.0 hp) at 50 Hz, 106.8 kW (143.0 hp) at 60 Hz.
    4. BMEP prime: 1702.0 kPa (246.9 psi) at 50 Hz, 1619.0 kPa (234.8 psi) at 60 Hz.
    5. BMEP standby: 1873.0 kPa (271.7 psi) at 50 Hz, 1781.0 kPa (258.3 psi) at 60 Hz.
    6. Regenerative power: 8.2 kW at 50 Hz, 13.8 kW at 60 Hz.
  7. Fuel System
    1. Fuel filter type: replaceable element.
    2. Recommended fuel: class A2 diesel.
    3. Fuel consumption prime at 50 Hz: 24.1 l/hr (6.4 US gal/hr) at 110% load, 21.9 l/hr (5.8 US gal/hr) at 100% load, 16.6 l/hr (4.4 US gal/hr) at 75% load, 11.7 l/hr (3.1 US gal/hr) at 50% load.
    4. Fuel consumption prime at 60 Hz: 29.3 l/hr (7.7 US gal/hr) at 110% load, 26.3 l/hr (6.9 US gal/hr) at 100% load, 19.9 l/hr (5.3 US gal/hr) at 75% load, 14.2 l/hr (3.8 US gal/hr) at 50% load.
    5. Fuel consumption standby at 50 Hz: 24.1 l/hr (6.4 US gal/hr) at 100% load, 18.2 l/hr (4.8 US gal/hr) at 75% load, 12.6 l/hr (3.3 US gal/hr) at 50% load.
    6. Fuel consumption standby at 60 Hz: 29.3 l/hr (7.7 US gal/hr) at 100% load, 21.9 l/hr (5.8 US gal/hr) at 75% load, 15.4 l/hr (4.1 US gal/hr) at 50% load.
  8. Air System 50 Hz / 60 Hz
    1. Air filter type: replaceable element.
    2. Combustion air flow standby: 6.3 m³/min (221 cfm) at 50 Hz, 7.8 m³/min (275 cfm) at 60 Hz.
    3. Combustion air flow prime: 6.0 m³/min (212 cfm) at 50 Hz, 7.8 m³/min (274 cfm) at 60 Hz.
    4. Maximum combustion air intake restriction: 8.0 kPa (32.1 in H₂O) at both frequencies.
    5. Radiator cooling air flow: 187.8 m³/min (6632 cfm) at 50 Hz, 244.2 m³/min (8624 cfm) at 60 Hz.
    6. External restriction to cooling air flow: 125 Pa (0.5 in H₂O) at both frequencies.
  9. Cooling System 50 Hz / 60 Hz
    1. Cooling system capacity: 17.5 l (4.6 US gal) at both frequencies.
    2. Water pump type: centrifugal.
    3. Heat rejected to water and lube oil standby: 50.7 kW (2883 Btu/min) at 50 Hz, 64.0 kW (3640 Btu/min) at 60 Hz.
    4. Heat rejected to water and lube oil prime: 46.1 kW (2622 Btu/min) at 50 Hz, 57.7 kW (3281 Btu/min) at 60 Hz.
    5. Heat radiation to room standby: 7.5 kW (427 Btu/min) at 50 Hz, 9.4 kW (535 Btu/min) at 60 Hz.
    6. Heat radiation to room prime: 6.8 kW (387 Btu/min) at 50 Hz, 8.5 kW (483 Btu/min) at 60 Hz.
    7. Radiator fan load: 2.8 kW (3.8 hp) at 50 Hz, 4.8 kW (6.4 hp) at 60 Hz.
  10. Exhaust System 50 Hz / 60 Hz
    1. Silencer type: industrial.
    2. Silencer noise reduction: SD50 (1).
    3. Pressure drop across silencer system: 2.10 kPa (0.620 in Hg) at 50 Hz, 3.56 kPa (1.051 in Hg) at 60 Hz.
    4. Silencer noise reduction level: 22 dB at 50 Hz, 17 dB at 60 Hz.
    5. Exhaust back pressure: 18.0 kPa (5.3 in Hg) at 50 Hz, 15.0 kPa (4.4 in Hg) at 60 Hz.
    6. Exhaust gas flow standby: 16.3 m³/min (576 cfm) at 50 Hz, 20.4 m³/min (720 cfm) at 60 Hz.
    7. Exhaust gas flow prime: 15.2 m³/min (537 cfm) at 50 Hz, 18.4 m³/min (650 cfm) at 60 Hz.
    8. Exhaust gas temperature standby: 543 °C (1009 °F) at 50 Hz, 574 °C (1065 °F) at 60 Hz.
    9. Maximum allowable back pressure: 514 (957) at 50 Hz, 517 (963) at 60 Hz.
  11. Alternator Performance Data
    1. Motor starting capability: 187 kVA at 415/240 V, 176 kVA at 400/230 V, 160 kVA at 380/220 V, 208 kVA at 220/127 V, 206 kVA at 480/277 V, 136 kVA at 380/220 V, 160 kVA at 240/120 V, 149 kVA at 230/115 V, 177 kVA at 440/254 V.
    2. Short circuit capacity: 300% for all voltage configurations.
    3. Reactances per unit: Xd 3.200, X'd 0.120, X''d 0.074 at 415/240 V; Xd 3.440, X'd 0.130, X''d 0.080 at 400/230 V; Xd 3.810, X'd 0.150, X''d 0.089 at 380/220 V; Xd 2.840, X'd 0.110, X''d 0.066 at 220/127 V; Xd 3.240, X'd 0.130, X''d 0.075 at 480/277 V; Xd 5.080, X'd 0.200, X''d 0.118 at 380/220 V; Xd 4.310, X'd 0.170, X''d 0.100 at 240/120 V; Xd 4.660, X'd 0.180, X''d 0.108 at 230/115 V; Xd 3.850, X'd 0.150, X''d 0.090 at 440/254 V.
    4. Reactances shown are applicable to standby ratings.
    5. Motor starting capability based on 30% voltage dip at 0.6 power factor.
    6. Short circuit capacity with optional permanent magnet generator or AREP excitation.
  12. Alternator Technical Data
    1. Manufacturer: OLYMPIAN.
    2. Model: LL3014B.
    3. Number of bearings: 1.
    4. Insulation class: H.
    5. Winding pitch code: 2/3 - 6.
    6. Wires: 12.
    7. Ingress protection rating: IP23.
    8. Excitation system