Phoenix, PXS-0.60, Thermal Oil Heater, 600,000 BTU/hr, 500 deg F, 50 GPM

Description

  1. Overview
    1. Unit will be complete and ready to fire after connecting to the electric, fuel, and hot oil circulation piping
    2. Pictures available
  2. Specifications
    1. Maximum design temperature: 500 degrees Fahrenheit
    2. Natural gas atmospheric burner rated at 760,000 btu/hr
    3. Heater maximum output: 600,000 btu/hr
    4. Based on a circulation of 50 gpm and a delta temperature of 50 degrees Fahrenheit
    5. The net exhaust gas temperature will not exceed the outgoing oil temperature by more than 100 degrees Fahrenheit
    6. In the lower oil temperature ranges (350 degrees Fahrenheit), this equates to 82% net efficiency
    7. In the upper temperature ranges (550-600 degrees Fahrenheit), this equates to 78% net efficiency
  3. Included Components
    1. 300 gallon expansion tank
    2. One 50 gpm hot oil circulation pump
    3. Bms (burner control)
    4. Oil temperature operating control
    5. Oil temperature high limit control
    6. Stack temperature high limit control
    7. Oil level switch with low oil level alarm
    8. Oil flow switch with low oil flow alarm