Air cooled salient, brushless 4-pole general electric (or equivalent) wpii generator
Open ventilation, air cooled, suitable for outdoor installation in a non-hazardous environment
Includes a brushless excitation system with permanent magnet generator
Neutral and line side cubicles are included
Reduction Gearbox
Epicyclic speed reducing gearbox located within the gas turbine enclosure
Designed to reduce the gas turbine speed to the generator speed
Unit Enclosure
Weatherproof acoustic enclosure
Completely assembled and mounted over the equipment
Turbine compartment is fully ventilated with belt driven fan
Explosion-proof lighting is provided in the compartment
Baseplate
Support structure for the gas turbine, gearbox, acoustic enclosure and auxiliary equipment
Generator is to be mounted directly onto the customer supplied foundation pad
Fabricated from w24 x 9 x 68 lbs/ft
Full depth transverse members provide rigid design suitable for installation in ubc seismic zone 3 (or equivalent) earthquake areas
Provides a convenient structure for transportation and provides the turbine/generator lube oil tank walls
Air Inlet System
Self-support combustion air filter and roof mounted ventilation air system
Combustion inlet air system includes a barrier air filter with weather louvers and a painted carbon steel air intake silencer with stainless steel splitters
Turbine Exhaust
Axial exhaust outlet with connection flange to facilitate in-line mounting to a hrsg or simple cycle exhaust stack
Expansion joint and silencer are not furnished
Fuel System
Natural gas dle fuel system using electronically controlled fuel metering valves
For full-load operation, the gaseous fuel must be supplied to the baseplate at a minimum of 334 psig and maximum of 363 psig
Lube Oil System
Common lube oil systems for the gas turbine, gearbox and generator
Internal surfaces of the integral carbon steel oil reservoir are epoxy coated
Piping is all stainless steel, and the lube oil system valves have stainless steel trim
Includes a main mechanical lube oil pump, a/c pre/post oil pump, emergency dc lube oil pump, duplex filters, fin fan coolers, fan-assisted air/oil separator, and electric heaters
Lube oil cooler is the only component in the lube oil system that is remotely mounted
Electro-Hydraulic Start System
Hydraulic starting system module that includes an electric motor driven hydraulic pump assembly, filters, reservoir and cooler
A hydraulic motor is mounted on the auxiliary gearbox
Fire Protection System
Installed fire protection system complete with hydrocarbon sensing and thermal detectors, piping and nozzles in the engine compartment
Requires cylinders (not furnished) containing co2 mounted on a separate module
A 24v dc battery and charger to power the fire protection system is also included
Gas Turbine Generator Control System
Freestanding control panel suitable for mounting in an indoor, non-hazardous area
Features an integrated electronic fuel management system with a plc based programmable sequencer
Power for the control panel is to be provided by a dedicated 24v dc lead acid battery systems (not furnished)
Wash System
Supplied with an "off-line" cleaning system
Request a Quote
✓
Request sent
Thank you, our team will reply to you shortly.
Direct access to our team
Email American Plant & Equipment
Tell us what you want to buy, source, finance, or sell. A machinery specialist will follow up with you.
✓
Thank you. Your request is with the American Plant and Equipment team.