Waukesha, VHP7044GSI, 1.055 MW, 1200 rpm, 480V, 60 Hz, Natural Gas Generator

Description

  1. Overview
    1. Can operate at 1150 kW, 1200 rpm, 60 Hz, 600/480 VAC
    2. Or at 1050 kW, 1000 rpm, 50 Hz, 400 VAC
    3. Weather enclosure with skid
    4. Engine driven radiator assembly
    5. Engine controls and interface: Waukesha engine ECU and auxiliary I/O box
    6. Kato alternator, 1200 kW / 1500 kVA, 6P6-3300, 6 poles, 2 bearing, 1200 rpm, 80 deg C temp. rise (40 deg. ambient), IP-23 enclosure, PMG, class “H”, 600/480 volt AC dual voltage, 3 ph, 60 Hz, 0.8 PF
    7. Four (4) units with Renold coupling; 4 units with Marathon alternator 480 VAC
    8. Engine controls and interface – ECU and auxiliary I/O box
  2. Oil and Gas Systems
    1. 50 gallon oil make-up system with level indication
    2. Inlet gas train with regulator, manual shutoff valve and solenoid – gas train piped to outside of enclosure
  3. Exhaust System
    1. 3-way exhaust catalyst and industrial exhaust silencer with heat blanket and exhaust flexible connection, exhaust stack – 4’ extension with rain cap
    2. Exhaust supports: structural frame to support catalyst and silencer from genset platform
  4. Enclosure and Platform
    1. Engine skid recessed-mounted into working skid - non-slip diamond plate floor
    2. Base frame designed to accommodate drop over, weather-proof enclosure lift-off frame, for (6)-point rig on/lift off from base / platform
    3. Removable lifting eyes
    4. Bolt-on connection to platform/base
    5. (2) single access doors
    6. (1) double access door
    7. Spill containment for engine coolant and oil, incorporated into working platform
    8. Front access only through double doors on alternator end of genset
    9. NEMA 3R rated
  5. Electrical and Controls
    1. Main generator circuit breaker
    2. 2000AF insulated case circuit breaker, fixed mounted, 600/480VAC NEMA 3R, 65k AIC, UL891
    3. LSIG trip, neutral sensor, 24VDC shunt trip, form ‘C’ aux contacts
    4. Copper ground bus
    5. Metering CT’s and PT’s
    6. CB open and close control by Deep Sea 8610 controller
    7. Deep Sea 8610 engine controller – parallel capable to utility - gen start/stop/shutdown, sync, island, load share (other Deep Sea gens) and utility parallel (adj. base load) modes of operation
    8. Cable connection, 600/480V, 2000A – alternator output to main CB, protected in steel wire way
    9. Exterior cable connection - copper bus with NEMA pads/holes designed to accept customer cables and lugs, designed for cable entry from ground level, at side of enclosure near double doors
    10. 480 V to 120/208V transformer 100 amp load center
    11. Interior lighting, receptacles, and cable tray - convenience receptacles – GFCI, (1) double socket each side of gen container, (1) near breaker/control cabinet
    12. DC emergency lighting each side of container, above access/escape doors with timer
    13. Exterior lighting – (2) elevated lights to maintain light at ground level, pre-wired and installed but shipped loose
    14. Light switches with weatherproof covers
    15. Flush mount emergency stop with break glass NEMA 3R, shipped with extra contact block
    16. Battery charger sens, battery box with spill containment
    17. Engine start batteries and containment
  6. Testing and Installation Notes
    1. 4 hour load test
    2. Any externally mounted items that must be removed for shipment are to be re-installed by the installing rigger / contractor