Description System Information Location: 6.6mw × 6set ac power plant Number of gen set size of unit dg.7 to dg.12 Engine manufacturer: Wartsila Finland Engine model: Wartsila Vasa 18v32d-ln Rated kw: 6,600 per unit Rpm: 720 Fuel consumption at 100% loading: 200 g/kw hr Generator manufacturer: ABB Generator model: ABB HSG 900xs8-xs10 Generator kw: 6,600 Voltage: 11,400 v Frequency: 60 hz Genset on concrete foundation: yes Platforms: yes Serial Numbers And Service Hours DG7: engine no. 21040, 25,862 hours (start 2001 to stop 2009) DG8: engine no. 21041, 25,603 hours (start 2001 to stop 2009) DG9: engine no. 21042, 25,688 hours (start 2001 to stop 2009) DG10: engine no. 21043, 11,173 hours (start 2001 to stop 2009) DG11: engine no. 21044, 25,100 hours (start 2001 to stop 2009) DG12: engine no. 21045, 23,729 hours (start 2001 to stop 2009) Mechanical System Starting system: compressed air system Starting air compressor: HL2/90 Air receiver module, service/starting: 7.5 bar × 1, 30 bar × 2 Air bottle Air receiver automatic drains: 1 set Charge air system Air filter: 3 sets DL-350/645 FU5 Silencer: 3 sets S/AVP DN600 Ducting flanges: DIN 2501/NP6 Cooling water system Cooling tower: 3 sets mechanical induced draft cross flow type Compensation tank Fuel system Day tank: 40 m³ Fuel meter DFO pre-pressure pump HFO system Fuel meter Fuel feeder/booster unit: AMB-A-018000 SS HFO buffer tank: 20 m³ HFO separator unit: Alfa Laval FOPX 613THD-20 HFO pressure circuit and circulation module: IMO ACE 032 NTBP T4B Lubrication oil system Circulation system pump: IMO ACG 060 N5 IVBM × 6 sets Lubrication oil service module / oil separator units: Alfa Laval LOPX 707 × 6 sets Lube circulating tank: 10.0 m³ × 6 sets Lube oil automatic filter: 6 sets FFP-2040 Heat recovery system Steam system Steam exhaust boiler: NKK × 6 sets Feed water tank Steam evaporation drum: NKK × 6 sets Blow down tank: × 6 sets Steam collector: × 1 set Dumping condenser with cooling water Steam plant switchgear Pipe insulation Exhaust gas system Silencer with supporting brackets: S/AV NS1000/25DBA × 6 sets Ducting Insulation Electrical System Main switch gear Main bus bar: 11.4 kv Generator cubicle: BAC011 / 0211, size 355 × 800 × 2288 mm, ABB Neutral point cubicle: BAN901, size 2400 × 1000 × 1700 mm, VEO / AR16810 Outgoing feeder cubicle: BAC903, size 1355 × 800 × 2288 mm, ABB Fused switch disconnect or cubicle: BAC902, size 1355 × 800 × 2288 mm, ABB / MH12025 Measuring cubicle: BAC901, size 1355 × 800 × 2288 mm, ABB / MH12026 Station service system Station auxiliary transformer: size 2800 × 2050 × 2400 mm, 1000 kva, 11.4 kv / 460 v Low voltage switchboard: size 1020 × 670 × 1100 mm, 150 kva, 460 v / 380 v Local panel × 2 (MCC1 / MCC2) DC system BEY901 DC board: size 837 mm × 400 mm × 1700 mm × 2, Vaasa Battery charger Input: 230 vac, output: 80-125 vdc × 3 MSR 110/12 Batteries (12 v × 9 cells) × 2 sets UXH70-12 Spare Parts And Tools Engine parts for 3000 hours service only Auxiliary equipment, some basic items for separators Special tools engine: 1 set Special tools separator: 2 sets Included Equipment List Generating sets: 6 sets (DG7 through DG12) Engine with base: Wartsila 18v32d-ln, 6 units Turbocharger: 12 units Generator (type DIG 71M/10): 7,760 kw / 13,800 volt / 60 hz, 6 units Charge air room: 6 units Fuel oil system Pump and filter: 1 unit Booster unit: 6 units Oil return unit: 6 units Separator unit: 1 unit Transfer unit: 1 unit Lubrication oil system Filter unit: 6 units Pre-lubrication oil pump: 6 units Heat exchanger: 6 units Separator unit: 6 units Compressed air system Starting air bottle: 2 units Compressor unit: 30 bar, 4 units Control system compressor: 1 unit Cooling system Heat exchanger: 6 units Expansion tank: 6 units Cooling tower set: 2 units Maintenance tank: 6 units Cooling tower filter: 4 units Electrical and automation system Neutral point cubicle: 1 unit Common control panel: CFA901 to 902 Engine control panel: CFC011 to 071, 6 units Engine control panel: CFE011 to 071, 6 units