Total weight with oil: 385 tonnes; insulating oil 74 tonnes
Done very little work
It is a transformer from a closed 500 MW coal fired power generation plant
Voltage And Current Ratings
Rated voltage ratio: 432,000 V +10/-15% in +10/-15 steps // 23,500 V
Winding: HV, position 1, voltage: 475,200 V, current: 729 A
Winding: HV, position 11, voltage: 432,000 V, current: 802 A
Winding: HV, position 26, voltage: 367,200 V, current: 943 A
Winding: LV, voltage: 23,500 V, current: 14,741 A
Vector group: YN d1
Impedance Voltage At 75 Degrees Celsius
Power MVA: 600, pair of windings: HV/LV, position 1, impedance voltage %: 17.3
Power MVA: 600, pair of windings: HV/LV, position 11, impedance voltage %: 16.5
Power MVA: 600, pair of windings: HV/LV, position 26, impedance voltage %: 15.8
Short-Circuit And Neutral Loading
Maximum permissible short-circuit duration: 3 s
Neutral loading capacity: HV-neutral is brought out fully insulated and grounded
Insulation Levels
Winding: HV, highest system voltage Um: 420 kV r.m.s., low frequency applied test voltage: 50 kV r.m.s., induced test voltage ACSD: 630 kV r.m.s., induced test voltage ACLD: 412/364 kV r.m.s., switching impulse withstand voltage SI: 1050 kV peak, lightning impulse withstand voltage LI FW/CW: 1,425/1,568 kV peak
Winding: HV-N, highest system voltage Um: 24 kV r.m.s., low frequency applied test voltage: 50 kV r.m.s., lightning impulse withstand voltage LI FW/CW: 126 kV peak
Winding: LV, highest system voltage Um: 24 kV r.m.s., low frequency applied test voltage: 50 kV r.m.s., lightning impulse withstand voltage LI FW/CW: 150/165 kV peak
Losses
No-load losses: 1.00 x Un 170,000 W
Load losses at 75 degrees Celsius: power 600 MVA, pair of windings HV/LV, position 1, load losses: 1,270,000 W
Load losses at 75 degrees Celsius: power 600 MVA, pair of windings HV/LV, position 11, load losses: 1,310,000 W
Load losses at 75 degrees Celsius: power 600 MVA, pair of windings HV/LV, position 26, load losses: 1,550,000 W
Total losses at 600 MVA: 1,480,000 W
Sound And Tap Changer
Sound pressure level Lpa: 70 dB + 0 dB tolerance without cooler at 0.3 m distance
Adjustment of transformer ratio under load by operation of on-load tap charger for voltage regulation: HV-side
On-load tap charger: Reinhausen, type VRF III 1000 Y – 123/D - 14261WS, position range +10/-15%, number of steps +10/-15, number of positions 26, rated current 1,000 A
Request a Quote
✓
Request sent
Thank you, our team will reply to you shortly.
Direct access to our team
Email American Plant & Equipment
Tell us what you want to buy, source, finance, or sell. A machinery specialist will follow up with you.
✓
Thank you. Your request is with the American Plant and Equipment team.
A machinery specialist will follow up with you.
Machinery updates
Subscribe to our email list
Tell us which industries you follow and we will send you the machines that match.
✓
You are on the list.
We will email you when machines that match your interests come in. Unsubscribe from any message.