Description Overview Titan 130-19500 combustion turbine generator 14.3 mw at sea level 59f no inlet or outlet losses 9,750 btu/kwh lhv new and clean no losses 59f Natural gas fired Solonox combustion system (< 25 ppmv nox) 60 hz Specifications 12.47kv generator 11,884 kw @.80pf 34.5/12.47 kv step up transformer Electric motor starting Inlet and exhaust ducting Self cleaning inlet air filter Outdoor enclosures Control cabinet, switchgear and mcc Condition Commissioned in dec/2001 5,500 fired hours baseline operation