Waukesha, VHP 7044GSI, Natural Gas Generator, 1150 kW, 60Hz, 1200 RPM (New)

Description

  1. Overview
    1. Weather enclosure with skid
    2. Engine driven radiator assembly
    3. Engine controls and interface: Waukesha engine ECU and auxiliary I/O box
    4. Renold coupling
    5. 50 gallon oil make-up system with level indication
    6. Inlet gas train with regulator, manual shutoff valve and solenoid – gas train piped to outside of enclosure
    7. 3-way exhaust catalyst and industrial exhaust silencer with heat blanket and exhaust flexible connection, exhaust stack – 4’ extension with rain cap
    8. Exhaust supports: structural frame to support catalyst and silencer from genset platform
    9. Engine skid recessed-mounted into working skid - non-slip diamond plate floor
    10. Base frame designed to accommodate drop over, weather-proof enclosure lift-off frame, for (6)-point rig on/lift off from base / platform
    11. Removable lifting eyes
    12. Bolt-on connection to platform/base
    13. (2) single access doors
    14. (1) double access door
    15. Spill containment for engine coolant and oil, incorporated into working platform
    16. Front access only through double doors on alternator end of genset
    17. NEMA 3R rated
  2. Generator Specifications
    1. Kato alternator, 1200 kW / 1500 kVA, 6P6-3300, 6 – poles, 2 bearing, 1200 rpm, 80 deg C temp. rise (40 deg. ambient), IP-23 enclosure, PMG, class “H”, 600/480 volt AC dual voltage, 3 ph, 60 Hz, 0.8 pf
    2. Main generator circuit breaker
    3. 2000AF insulated case circuit breaker, fixed mounted, 600/480 VAC NEMA 3R, 65 kAIC, UL891
    4. LSIG trip, neutral sensor, 24 VDC shunt trip, form ‘C’ aux contacts
    5. Copper ground bus
    6. Metering CT’s and PT’s
    7. CB open and close control by Deep Sea 8610 controller
    8. Cable connection, 600/480 V, 2000 A – alternator output to main CB, protected in steel wire way
    9. Exterior cable connection - copper bus with NEMA pads/holes designed to accept customer cables and lugs, designed for cable entry from ground level, at side of enclosure near double doors
  3. Control and Electrical Systems
    1. Deep Sea 8610 engine controller – parallel capable to utility - gen start/stop/shutdown, sync, island, load share (other Deep Sea gens) and utility parallel (adj. base load) modes of operation
    2. 480 V to 120/208 V transformer
    3. 100 amp load center
    4. Interior lighting, receptacles, and cable tray - convenience receptacles – GFCI, (1) double socket each side of gen container, (1) near breaker/control cabinet
    5. DC emergency lighting each side of container, above access/escape doors with timer
    6. Exterior lighting – (2) elevated lights to maintain light at ground level, pre-wired and installed but shipped loose
    7. Light switches with weatherproof covers
    8. Flush mount emergency stop with break glass NEMA 3R, shipped with extra contact blocks
    9. Battery charger sens, battery box with spill containment
    10. Engine start batteries and containment
  4. Testing and Installation Notes
    1. 4 hour load test