Description Overview Gas turbine generator set: 100 MW Frequency: 60 Hz Fuel: LNG Year: 1995 Stopped operation: June 2013 Gas Turbines Manufacturer: Westinghouse (Siemens) Model name: W501D5 Type: Axial flow Power output: 100,000 kW (100 MW) Stages: 4 stages Inlet temperature: 1093 °C Exhaust temperature: 530 °C Exhaust flow: 1,313,272 kg/h TAC temperature: 15 °C Speed governor: DEHC Starter System Type: Electric motor Capacity: 1530 kW Quantity: 1 each Combustor Type: Can-annular Quantity: 14 each Compressor Type: Axial flow Air mass flow: 358 Nm³/min Inlet temperature: 15 °C Pressure ratio: 14:1 Outlet pressure: 14.462 kg/cm² Stages: 19 stages Outlet temperature: 389 °C Generators Manufacturer: Westinghouse (Siemens) Type: OAC (open-air-cooled) Rated power: 129 (143) MW (MVA) Power factor / short-circuit ratio: 90% / 0.695 Frequency: 60 Hz / 2 pole Speed: 3600 RPM Rated voltage / current: 13.8 kV / 5731 A Insulation class: F Exciter Speed: 3600 RPM Exciter type: PMG Rated voltage / current: 325 V / 1006 A Protection devices: 87G, 59GN, 40, 32, 46, 51V, 60, 25 Neutral grounding: NGR Bus bar: IPB (3 phases) Rotation direction: CW (viewed from exciter end) Operation Hours Gas turbine: 37,000–40,000 hours Operation hours from overhaul to stop: gas turbine 15,000–18,000 hours Scope of Supply Turbine Generator Control panel (electric package) Switchgear box Mechanical room equipment Condition Currently installed and dismantled