Description Overview Gas turbine generator set: 100 mw x 4 units Hz: 60 hz Fuel: lng Year: 1995 Stopped operation: june 2013 Gas Turbines Manufacturer: westinghouse (siemens) Model name: w501d5 Type: axial flow Power output: 100,000 kw (100 mw) Stages: 4 stage Inlet temp.: 1093 ℃ Exhaust temp.: 530 ℃ Exhaust flow: 1313272 kg/h Tac temp.: 15℃ Speed governor: dehc Starter System Type: electric motor Capacity: 1530 kw Quantity: 1 ea Combustor Type: can-annular Quantity: 14 ea Compressor Type: axial flow Air mass flow: 358 n㎥/min Inlet temp.: 15℃ Pressure ratio: 14:01 Outlet pressure: 14.462 kg/㎠ Stages: 19 stage Outlet temp.: 389 ℃ Generators Manufacturer: westinghouse (siemens) Type: oac (open-air-cooled) Rated power: 129 (143) mw (mva) Power factor/ short-circuit ratio: 90%/0.695 Frequency: 60 hz/2 pole Speed: 3600 rpm Rated voltage/current: 13.8 kv/5731 a Insulation class: f Exciter Speed: 3600 rpm Exciter type: pmg Rated voltage/current: 325 v/1006 a Protection devices: 87g, 59gn, 40,32,46, 51v, 60,25 Neutral grounding: ngr Bus bar: ipb (3 phases) Rotation direction: cw (viewed from exciter end) Operation Hours Gas turbine #2: 37,013 hours (1996.1~2013.6) Gas turbine #3: 39,800 hours (1996.1~2013.6) Gas turbine #5: 41,819 hours (1996.7~2013.6) Gas turbine #6: 40,524 hours (1996.7~2013.6) Operation Hours From Overhaul to Stop Gas turbine #2: 16,611 hours Gas turbine #3: 17,098 hours Gas turbine #5: 17,978 hours Gas turbine #6: 16,921 hours Scope of Supply Turbine Generator Control panel (electric package) Switchgear box Mechanical room equipment