MAN, E3262 LE202, 2017, Gas CHP Plant, 530 kWe / 559 kWth, Biogas or Natural Gas, 400 V, 45,699 Hours, Containerized

Description

  1. Overview

    1. 45,699 operating hours

    2. Fuel: biogas or natural gas

    3. Water cooled

  2. Electrical Specifications

    1. Electrical output 530 kW (710.7 hp)

    2. Nominal apparent power 660 kVA

    3. Power factor 0.95

    4. Electrical efficiency 39%

    5. Voltage 400/230 V

  3. Thermal Specifications

    1. Thermal output 559 kW (749.6 hp)

    2. Thermal efficiency 41%

    3. Fuel input 1,358 kW (1,821.1 hp)

    4. Heat recovery from cooling water 264 kW (354.0 hp)

    5. Heat recovery from mixture HT 75 kW (100.6 hp)

    6. Heat recovery from exhaust gas 220 kW (295.0 hp)

  4. Generator

    1. Leroy Somer LSA 49.1 generator

    2. Generator rating 660 kVA

  5. Condition And Maintenance

    1. Major overhaul December 2025

    2. Turbocharger replaced April 2026

    3. Ready for operation, fully functional

  6. Included Equipment

    1. Container

    2. Switchgear cabinet

    3. Oil tanks

    4. Plate heat exchanger

    5. Exhaust stack

    6. Exhaust gas heat exchanger

    7. Documentation included