NovaStar, GG136, Pad-Mounted Transformer, 500 kVA, 34.5 kV to 480Y/277 V, 60 Hz (New)

Description

  1. Overview

    1. New, unused three-phase liquid-immersed pad-mounted distribution transformer for outdoor distribution

    2. Quantity: 2 units; a third unit can be supplied

    3. Radial feed

    4. Carbon steel enclosure, NEMA 3R

    5. Design standard IEEE/ANSI C57.12.34; tested to IEEE C57.12.90

  2. Electrical Ratings

    1. Rated capacity: 500 kVA each

    2. Primary voltage: 34.5 kV, delta

    3. Secondary voltage: 480Y/277 V, wye, 4-wire; neutral fully insulated and brought out

    4. Vector group: Dyn1

    5. Frequency: 60 Hz

    6. Impedance: 5.75%

    7. BIL: 150 kV high voltage / 30 kV low voltage

    8. Tap changer: plus or minus 2 x 2.5%, off-circuit

    9. Temperature rise: 65 K

    10. No-load loss: 0.9 kW or less; load loss: 7.5 kW or less

  3. Construction

    1. Copper windings

    2. Core of high-grade CRGO silicon steel

    3. Dead-front high voltage bushings, 200 A loadbreak

  4. Insulating Fluid Options

    1. Option A: mineral oil, cooling class ONAN

    2. Option B: FR3 natural ester, cooling class KNAN (higher fire point)

  5. Included Equipment and Accessories

    1. Two-position loadbreak switch

    2. Bay-o-net and current-limiting fuses

    3. Pressure relief valve

    4. Oil level sight glass and dial thermometer

    5. Drain valve and filling plug

    6. Grounding provisions

    7. Lifting lugs and jacking pads

  6. Dimensions and Weight (approximate)

    1. Overall dimensions: 1,800 x 1,700 x 2,000 mm (70.9 x 66.9 x 78.7 in)

    2. Total weight: about 2,100 kg (4,630 lb)

    3. Insulating fluid volume: about 350 liters (92 US gal)

    4. Final details, dimensions and weights are confirmed through approved drawings

  7. Documentation Available

    1. General arrangement drawing, English nameplate example, routine test documentation and applicable type test reports