Description OverviewNew, unused three-phase liquid-immersed pad-mounted distribution transformer for outdoor distributionQuantity: 2 units; a third unit can be suppliedRadial feedCarbon steel enclosure, NEMA 3RDesign standard IEEE/ANSI C57.12.34; tested to IEEE C57.12.90Electrical RatingsRated capacity: 500 kVA eachPrimary voltage: 34.5 kV, deltaSecondary voltage: 480Y/277 V, wye, 4-wire; neutral fully insulated and brought outVector group: Dyn1Frequency: 60 HzImpedance: 5.75%BIL: 150 kV high voltage / 30 kV low voltageTap changer: plus or minus 2 x 2.5%, off-circuitTemperature rise: 65 KNo-load loss: 0.9 kW or less; load loss: 7.5 kW or lessConstructionCopper windingsCore of high-grade CRGO silicon steelDead-front high voltage bushings, 200 A loadbreakInsulating Fluid OptionsOption A: mineral oil, cooling class ONANOption B: FR3 natural ester, cooling class KNAN (higher fire point)Included Equipment and AccessoriesTwo-position loadbreak switchBay-o-net and current-limiting fusesPressure relief valveOil level sight glass and dial thermometerDrain valve and filling plugGrounding provisionsLifting lugs and jacking padsDimensions and Weight (approximate)Overall dimensions: 1,800 x 1,700 x 2,000 mm (70.9 x 66.9 x 78.7 in)Total weight: about 2,100 kg (4,630 lb)Insulating fluid volume: about 350 liters (92 US gal)Final details, dimensions and weights are confirmed through approved drawingsDocumentation AvailableGeneral arrangement drawing, English nameplate example, routine test documentation and applicable type test reports