Description OverviewNew three-phase pad-mounted distribution transformer, 500 kVA, 34.5 kV primary to 480Y/277 V secondary, 60 HzQuantity available: 2 unitsUL Listed; built and tested to IEEE C57.12.00, IEEE C57.12.90 and IEEE C57.12.28; DOE 2016 efficiency compliantOutdoor pad-mounted design, dead front, loop/radial switch (2-position T-blade)RatingsRated capacity: 500 kVAPrimary voltage: 34.5 kV, taps plus/minus 2 x 2.5%, 5-position tap changerSecondary voltage: 480Y/277 VVector group: Dyn11Frequency: 60 Hz, three phaseImpedance: 6.5% (plus/minus 10%)No-load losses: 0.68 kW; load losses: 6.91 kW (at 85 °C); efficiency 99.53%BIL: 200 kV HV / 30 kV LVWindings: copperCooling and InsulationMineral oil, ONAN (FR3 natural ester, KNAN, available as an option)Temperature rise: 65 °C winding, 55 °C top oilNoise level: under 58 dB (NEMA TR1)Dimensions and WeightHeight: 76.8 in (1,950 mm); width: 69.3 in (1,760 mm); length: 70.9 in (1,800 mm)Total weight: about 5,137 lb (2,330 kg), of which oil 1,345 lb (610 kg)Standard ComponentsVacuum pressure gauge, pressure relief valve, oil filler, oil level indicator, dial temperature gaugeBayonet fuses with backup fuses6 HV bushing wells (dead front) with cable connectors; 4 LV stud bushings with 8-hole spadesOil drain valve with sampler, lifting lugs, IEEE two-hole ground pads, penta-head cabinet bolts