NovaStar, GG139, Resistive Load Bank, 1,250 kW, 240/480 V, 3-Phase 4-Wire, 60 Hz, Automatic PLC Control (New)

Description

  1. Overview

    1. New build AC resistive load bank for testing generators, UPS systems, inverters and power supplies, automatic operation

    2. Forced air cooling with horizontal air inlet and horizontal air outlet

  2. Electrical Specifications

    1. Total capacity: 1,250 kW (1,676 hp) at unity power factor

    2. Rated voltage: 240/480 VAC, 3-phase 4-wire, 60 Hz

    3. Load steps: 1 kW x 1, 2 kW x 2, 5 kW x 3, 10 kW x 3, 25 kW x 6, 50 kW x 4, 100 kW x 2, 200 kW x 3, all in parallel

    4. Fe-Cr-Al resistive elements, continuous duty, up to 110 C (198 F) above ambient

    5. Protections: over voltage, short circuit, overload and cooling fan failure, earth fault, high internal temperature

  3. Controls

    1. Separate PLC control panel with 7 in HMI, all metering and control through the HMI

    2. Monitoring of kW, voltage, current, power factor and load bank temperature

    3. Graphs exported as JPG and data in Excel format

  4. Construction

    1. Heater section and control panel in two enclosures; mild steel sheet body on an angle iron frame

    2. Halogen-free fire-retardant low-smoke cables, ETP copper bus bar

    3. Lifting lugs and caster wheels; operating ambient -10 to +50 C (14 to 122 F)

    4. Recommended housing: a trailer-mountable container, 6,700 x 2,400 x 2,400 mm (263.8 x 94.5 x 94.5 in), 4,500 kg (9,921 lb)

  5. Included

    1. Maintenance tool set, spare fuses, 2 step contactors, PLC application program, spare lamps and push buttons

    2. 3 sets of operating and maintenance manuals, laminated control drawing in the panel