Caterpillar, 3512B, Major Overhauled Diesel Generator Sets, 1,360 kW Prime, 600 V, 60 Hz, 1,200 RPM

Description

  1. Overview

    1. 6 Caterpillar 3512B diesel generator sets, major overhauled

    2. Prime output 1,360 kW (1,823.8 hp) / 1,700 kVA at 0.8 power factor, continuous prime duty

    3. Standby output 1,500 ekW / 1,875 kVA (short-term only)

    4. 600 V, 60 Hz, 3 phase, 1,200 RPM

    5. Suitable for continuous land drilling rig operation

  2. Engine

    1. Caterpillar 3512B TA, V-12, turbocharged and aftercooled, four-stroke, water cooled

    2. Major overhaul to Caterpillar SIS procedures, wear limits and tolerances

    3. Liners, piston rings, main and rod bearings, valves and seats, injectors, turbocharger cartridges, oil pump and fuel transfer pump replaced or repaired to overhaul tolerances

    4. Electronic governing with ADEM A3 engine control module; electronic unit injection

    5. Dynamometer run-in and performance test with Caterpillar ET report

  3. Cooling System (New)

    1. New package-mounted radiator for 55 °C (131 °F) ambient

    2. New fan, fan drive, belts and guards

    3. New jacket water pump, separate circuit aftercooler pump, thermostats and housings

    4. New aftercooler core with anti-corrosion coating

  4. Alternator (New)

    1. New brushless, self-excited, salient pole, 6-lead alternator, 600 V / 60 Hz

    2. Class H insulation, IP23

    3. Voltage regulation plus or minus 0.5%, reactive droop, kVAR / PF mode

  5. Controls and Starting

    1. EMCP 4.4 control panel with paralleling, load sharing and grid synchronization

    2. Full engine and generator protections: over and under voltage and frequency, overcurrent, reverse power, overspeed, low oil pressure, high water temperature, low coolant level

    3. 24 V DC electric start with battery rack, cables and battery disconnect switch; 45 A charging alternator

  6. Testing and Documents

    1. Full load test, 80% load step transient test to ISO 8528-5, paralleling test and protection checks

    2. Per unit, in English: overhaul scope and parts list, dynamometer report, alternator test report, cooling system pressure test record, load and paralleling test report, EMCP settings and wiring diagram, operation and maintenance manual

  7. Supply per Set

    1. Overhauled engine, new radiator, new fan and drive, new cooling pumps and thermostats, new aftercooler core, new alternator, EMCP 4.4 panel, 24 V DC starting system

    2. Standard accessories: air filters, exhaust elbow and silencer, anti-vibration mounts, lifting frame, filters, coolant

    3. Not included: site installation, civil works, exhaust ducting, fuel tank, paralleling cables, remote monitoring

  8. Warranty

    1. 12 months or 5,000 operating hours, whichever comes first, on the overhaul and on the new cooling system and alternator