Elin Motoren, HTM190E04, Gas Power Plant, 12MW, 6.6kV, 50Hz

Description

  1. Overview
    1. Rated system voltage: 6.6 kV
    2. Rated frequency: 50 Hz
    3. Number of phases: 3
    4. System earthing: neutral resistor
    5. Earth fault current: 5 A per generator
    6. Duty type: S1
    7. Insulation thermal class stator/rotor: F/F, vacuum impregnated
    8. Temperature rise class stator/rotor: B/B
    9. Neutral earthing resistor rating: 5 A, 10 sec
    10. Excitation: brushless (PMG)
  2. Construction
    1. According to standard: DS/EN 60034
    2. Degree of protection outdoor IP: 56
    3. Degree of protection indoor IP: NA
    4. Winding temperature detection: PT100 in each phase
    5. Vibration detectors required: yes, proximity type probes
    6. Preformed for portable earthing apparatus: yes
    7. Space heater: yes
    8. Painting specification: C086-TECH-M-SA-0007 external painting specification
  3. Environmental Conditions
    1. Hazardous area classification: EX II 3G EX PZ E IB IIB T3 GC
    2. Ambient temperature °C: min. -6.9, max. +25 (design +40 °C)
    3. Humidity %: 95
  4. Project Requirements
    1. Tag no.: 80-EG-0001A/B/C
    2. Service: continuous in N+1 configuration (3 x 50%)
    3. Manufacturer: ELIN Motoren
    4. Type: HTM190E04
    5. Location / module: weather deck
    6. Job no.: C086-TECH-E-SA-0012
    7. Required power: 15000 kVA
    8. Rated voltage: 6.6 kV
    9. Power factor cos phi: 0.773
    10. Location indoor/outdoor: offshore in noise hood
    11. Direct axis subtransient reactance, Xd" unsat/sat %: 16.8 % unsat / 14.0 % sat
    12. Direct axis transient reactance, Xd' unsat/sat %: 22.7 % unsat / 21.6 % sat
    13. Direction of rotation facing shaft end CW/CCW: CCW
    14. Max. allowable continuous harmonics (THD) %: 5
    15. Vibration detectors type: proximity type
  5. Cooling
    1. Cooling method IC: IC8A1W7
    2. Cooling medium: seawater
    3. Cooling water supply temperature max/min °C: refer to C086-TECH-Z-FD-0001 project design basis
    4. Cooling water supply pressure max/min bar g: refer to C086-TECH-Z-FD-0001 project design basis
  6. Cables and Terminals
    1. Main terminal boxes degree of protection IP: 56
    2. Main terminal boxes material: painted steel / stainless steel
    3. Number of power cables: 3 per phase
    4. Power cable size n x mm²: (1 x 300 mm²)
    5. Power cable outer diameter mm: 43.3
    6. Cable entry type gland/MCT/other: gland (Technip scope of supply)
    7. Auxiliary terminal boxes degree of protection IP: 56
    8. Auxiliary boxes material: painted steel / stainless steel
    9. Other cables (specify): neutral: 1 cable, 6/10 kV, 25.4 mm
    10. Phase connection of cables on generator terminals for CCW rotation: V1 U1 W1
  7. Generator Specifications
    1. Manufacturer: ELIN Motoren GmbH
    2. Type: HTM190E04
    3. Degree of protection IP: 56
    4. Frame size (IEC): IM 1005 (B3)
    5. Rotor type salient poles/cylindrical: cylindrical
    6. Synchronous speed rpm: 1500
    7. Direction of rotation facing shaft end CW/CCW: counter-clockwise
    8. Overall dimension (L x W x H) mm: approx. 5000 x 3000 x 3100, see GA drawing for details
    9. Dimensional drawing no.: C086-TECH-E-XD-3400-001 / 10001393723
    10. Weight of overall machine kg: 32000
    11. Weight of rotor kg: 7861
    12. Weight of exciter kg: 1101
    13. Weight of heat exchanger, dry kg: 331 (each cooler bundle)
    14. Weight of coolant kg: 16
    15. Prime mover moment of inertia J = GD²/4 kg m²: 745 (GT incl. gear)
    16. Generator moment of inertia J = GD²/4 kg m²: 735
    17. Rated voltage kV: 6.6
    18. Rated frequency Hz: 50
    19. Rated power output, Sn MVA: 15
    20. Rated power factor cos phi: 0.773
    21. Duty type: S1
    22. Rated current A: 1312
    23. Max. allowable negative phase sequence current %: 9
    24. Max. allowable continuous harmonics (THD) %: acc. IEC 5 %; acc. references 0.2 %
    25. Efficiency at 1/1 and 3/4 load %: 97.78; 97.79 - at cos phi 0.773
    26. Field current no load A: 99
    27. Field current rated load A: 270
    28. Insulation class stator/rotor: F / F
    29. Temperature rise class stator/rotor: B / B
    30. Overload capability % for hours: acc. DS/EN 60034-3; 4.15
    31. Overload capability % for seconds: acc. DS/EN 60034-3; 4.15
    32. Sustained short-circuit % for seconds: acc. DS/EN 60034-3; 4.16
    33. Short circuit ratio: 0.56
    34. Direct axis subtransient reactance Xd" unsat %/±: 16.8; tol. acc. DS/EN 60034-3; 4.19
    35. Direct axis subtransient reactance Xd" sat %/±: 14
    36. Quadrature axis subtransient reactance Xq" %/±: 20.4
    37. Direct axis transient reactance Xd' unsat %/±: 22.7
    38. Direct axis transient reactance Xd' sat %/±: 21.6
    39. Quadrature axis transient reactance Xq' %/±: 7.5
    40. Direct axis synchronous reactance Xd unsat %/±: 20
    41. Quadrature axis synchronous reactance Xq unsat %/±: 19.2
    42. Negative phase sequence reactance X unsat %/±: 18.6
    43. Negative phase sequence reactance X sat %/±: 15.7
    44. Zero phase sequence reactance Xo unsat %/±: 7
    45. Zero phase sequence resistance %/±: 6
    46. Stator winding leakage reactance XL %/±: 12
    47. Stator winding DC resistance %/±: -
    48. Negative phase sequence winding resistance %/±: -
    49. Positive phase sequence winding resistance %/±: -
    50. Direct axis S.C. subtransient time constant Td" sec: 0.02
    51. Direct axis O.C. subtransient time constant Tdo" sec: 0.03
    52. Quadrature axis S.C. subtransient time constant Tq" sec: 0.03
    53. Quadrature axis O.C. subtransient time constant Tqo" sec: 0.11
    54. Direct axis S.C. transient time constant Td' sec: 0.44
    55. Direct axis O.C. transient time constant Tdo' sec: 4
    56. D.C. time constant Ta sec: 0.24
    57. Cooling method IC: IC8A1W7
    58. Cooling water flow rate max/min m³/hr: ~ 26
    59. Cooling water design temperature °C: inlet temperature 4-12 (C086-TECH-Z-FD-0001)
    60. Cooling water design pressure max/min bar g: 14; test pressure 21
    61. Leak detection system: yes
    62. Winding temperature sensors type/number of: PT100
    63. Vibration detectors type/number of: yes; Bently Nevada-series 3300
    64. Heat exchanger material: CuNi10Fe
    65. Bearing drive end type/number of: Zollern / ZMZLB 22-250
    66. Bearing non drive end type/number of: Zollern / ZMZLQ 22-250
    67. Thrust bearing type/number of: NA
    68. Allowed axial thrust N: 0, no axial bearing in generator
    69. Bearing lubrication system incl./not incl.: lube oil supply by gas turbine oil system
    70. Lubricant ISO VG: cc. DIN 51 515, ISO viscosity class VG46
    71. Bearing temperature detectors type/number of: one duplex RTD per bearing
    72. Lubrication oil pressure bar g: 1.1 - 3.5
    73. Lubrication oil temperature °C: 55
    74. Sound pressure level Lp dBA: 80 +3 dB tolerance
    75. Coupling type: forged flange coupling
    76. Painting specification NORSOK / other: NORSOK as amended by C086-TECH-M-SA-007
  8. Exciter
    1. Type and manufacturer: DEV55G16 / VUES
    2. Rated current A: 270
    3. Rated voltage V: 242
    4. Insulation class stator/rotor: F / F
    5. Temperature rise class stator/rotor: B / B
    6. Pilot exciter rated current A: 7.5
    7. Pilot exciter rated voltage V: 56
    8. Excitation system description, enclosure: AC exciter with PMG; BGU bridge
  9. Automatic Voltage Regulator
    1. Type and manufacturer: Basler DECS 200 N
    2. Voltage stability, full operating range ±%: 0.25% (see note 1)
    3. Voltage drift, full operating range ±%: 0