MTU, 16V4000G63, 2017, 30.5 MW, 50 Hz, 15x Containerized Diesel Generator Sets

Description

  1. Overview
    1. Fifteen MTU 16V4000G63 exhaust emission optimized diesel engines coupled to high performance Mecc Alte ECO46 2L/4A alternators
    2. Rated at 2546 kVA / 2033 kW standby power and 2303 kVA / 1842 kW prime power
    3. 1500 rpm
    4. 400 volt, 50 Hz
    5. Year of manufacture: 2017 to 2018
    6. Only 150 to 200 hours since new
  2. Container And Enclosure
    1. Each generator is housed in a 40 ft sound attenuated container
    2. Skid mounted radiator designed for high end temperatures
    3. 40 ft hi cube container with switch gear room and control room
    4. Complete power plant in module design that can be easily transported and set up within days to generate a steady stream of electrical power
  3. Engine Specifications
    1. Engine: MTU 16V4000G63 exhaust emission optimized engine
    2. Engine speed: 1500 rpm
    3. Starting system: 24V electric with Optima yellow top batteries and battery isolator
    4. Engine governor: ADEC
  4. Alternator Specifications
    1. Alternator: Mecc Alte ECO46 2L/4A with MAUX excitation, oil primer and centrifuge fitted as confirmed by MTU
    2. Set mounted 4000A 4P motorized breakers
  5. Radiator Specifications
    1. Radiator: Skid mounted radiator designed for high end temperatures
    2. Radiator design: Tecno Group TG00094AA 30 m/s reduced airflow radiator with electric powered cooling fan
  6. Electrical And Control System
    1. Power box: CP6
    2. Model: HMW-2200-T5 STD 2200 kVA V400 / 50 Hz AS20
    3. Voltage: 400V, 3PH, 50 Hz
    4. Control panel: AS5 with free issue Comap IG-NTC-BB + Intelivision 5 components
    5. Air circuit breaker panel: 4 pole, 4000A Schneider NW04 motorized H2 100 kA breaking capacity with Micrologic 6.0A trip unit
    6. Heater: Thermostatically controlled 9 kW 400V 3 phase water jacket heater with circulation pump
    7. Battery charger: DeepSea DSE9470 10A intelligent mains battery charger
    8. Including: Automatic electric pre-lube pump; set mounted 2000A neutral earthing contactor with CT; fuel return cooler; centrifugal oil filter (MTU) and primary water separator filter
  7. Transformers
    1. Quantity 4: 4 MVA GBE oil immersed, free breathing step up power transformers with oil conservator and copper windings; 3 phase, 400-33 kV; 50 Hz
    2. Quantity 1: 2 MVA GBE oil immersed, free breathing step up power transformers with oil conservator and copper windings; 3 phase, 400-33 kV; 50 Hz
  8. Hv Switchgear Container
    1. Purpose built 40 ft hi cube container with heating, lighting and power installed
    2. Lined with rock wool insulated panels includes high level louver with fan and low-level louver for natural air flow
    3. Split into two sections/rooms with a control room on one side and switch gear in the other room with 33 kV ABB Ring Safe switchgear
  9. Control System
    1. Remote communication and load summation control panel (RCLSP)
    2. 1 x Comap IM-NTC BB base box controller (site load value monitoring and integration)
    3. 1 x Comap IBNT internet bridge (broadband interface)
    4. 1 x Comap ILB+ local bridge (local and PC remote interface)
    5. 1 x 230/240V DC PSU
    6. 1 set of control miniature circuit breakers
    7. 1 set of CAN bus interface terminals
    8. Beldon 3106A CANbus communication cabling and Cat 5E ethernet communication cables
    9. Comap MainSPro G59-3 protection relay (over/under volts, Hz and vector shift)
  10. Fuel Tank System
    1. Quantity 4 x 40,000L fuel tanks; double skinned; DD50 fuel polishing system; bund alarm; overfill alarm and contents gauge with adjustable volt free level alarm
    2. Quantity 1 x 20,000L fuel tanks; double skinned; DD50 fuel polishing system; bund alarm; overfill alarm and contents gauge with adjustable volt free level alarm