Description Overview Vitomax 200 HS type M235 037 ÜH Year 2007 Nominal steam output of 12 tph, 13 bar Heating: natural gas Boiler purpose: production of steam for heating buildings, hot water production technology Boiler type: stationary medium pressure steam boiler Fuel: natural gas Designation of the boiler: “K1” left, fire-tube boiler flame with three strokes with pressure furnace Specifications Allowable working pressure: 13 bar (1.3 MPa) Test pressure: 24.1 bar (2.41 MPa) Minimum burner output: 2.3 MW Nominal burner power: 10.0 MW Boiler output: 8 MW Thermal power boilers: 8.51 MW Permissible temperature steam according to label data: 260 °C Rated steam temperature according to the technical specifications of delivery: 225 °C Nominal feed water temperature: 103-105 °C Water volume of the packed boiler / at operating level: 28400/22600 L Specified efficiency of thermal energy production fuel boilers: Ø 95.00% The boiler was operated a total of 10,962 hours Burner Jaroslav Vlcek - heat and combustion technology Ltd. Prerov Type AVP 10 SN 1067, year of manufacture 2007 Nominal output of 10 MW Minimum power of 2.3 MW Fuel pressure 100 kPa Condition And Maintenance Steam boiler dismantled and secured The boiler was carried out regular inspections according to the decree for power equipment 4 x yearly operational review 1 x yearly leak test 1 x yearly adjustment of the burner 2 x yearly revision BOSB elements 1 x yearly emission measurements Included Water treatment installation with feed water pumps