Siemens, SGT-800, 2000, 54MW, 50Hz, Gas Fired Turbine (New)

Description

  1. Overview
    1. Siemens SGT-800 54 MW 50 Hz gas fired turbine
    2. Year: 2000
    3. New, properly stored and comes with full Siemens warranty
    4. “Single lift” fast track package
  2. Design Requirements
    1. Minimum outdoor temperature: -15 °C
    2. Maximum outdoor temperature: 55 °C
    3. Minimum lifting temperature: -15 °C
    4. Minimum transport temperature: -15 °C
    5. Altitude: <1000 meters above sea level
    6. Package location: outdoor
    7. Seismic loads according to IBC
    8. Acceleration short period, Ss, up to and including 1.5 g
    9. Acceleration long period, S1, up to and including 0.625 g
    10. Wind speed: 45 m/s according to IBC
    11. Non-hazardous area
    12. Near field sound pressure level: 85 dB(A)
    13. Electrical utility frequency: 50 Hz
    14. Auxiliary voltage: 400 VAC
  3. General Specifications
    1. KKS designation system
    2. Welded thermowells for gas fuel system and 1/2” NPT threaded for other auxiliaries
    3. Electrical and control panels in light grey, RAL 7035
    4. Warranty as defined in commercial terms and conditions
    5. Air cooled coolers for all equipment
    6. Surface treatment for indoor equipment according to ISO 12944-2:1998, category C3 medium
    7. Surface treatment for outdoor equipment according to ISO 12944-2:1998, category C4 high
    8. Enclosure internal equipment according to category C2
    9. Galvanized carbon steel according to ISO 1461:1999
    10. Surface treatment for electric generator according to ISO 12944-2:1998, category C5-I
    11. Enclosure exterior surface in pebble grey, RAL 7032, top coat color
    12. Life cycle assessment according to ISO 14040-43 available, containing quantifications of resource depletion, waste generation and emissions
  4. Codes and Standards
    1. Base frames: EN 1993 Eurocode
    2. Bolts and nuts: ASME standards
    3. Control cubicles: EN 60439 (corresponding to IEC 60439)
    4. Couplings: API 671 with comments
    5. Enclosures: EN 1993 Eurocode
    6. Pressure vessels, filters and coolers: ASME VIII excluding U-stamp
    7. Flanges: ANSI B16.5 on package piping and interconnecting piping
    8. Units: SI-units, exception: pressure (bar)
    9. Noise generating equipment: ISO 11204 and ISO 10494
    10. Other electrical equipment: EN 60204 (corresponding to IEC 60204)
    11. Pipe coupling threads: NPT and/or ISO threads
    12. Pipes: EN 13480 with dimensional standards according to ASME B31.3
    13. Pumps: DIN and ISO standards
    14. Vibration measured equipment: ISO 10816-4
    15. Vibration monitoring: API 670 with comments
    16. Drawings: ISO 5457
    17. Structural steel: EN 1993 Eurocode with additional compliance with IBC 2009
    18. Cable joints of M-type: EN 50262
    19. Balancing: ISO 1940-1 and ISO 11342
    20. Air intake filter: first stage filters EN 779:2012, second stage filter EN 1822:2009
    21. Gas fuel system: ISO 21789
    22. Lube oil unit: EN 60034 (corresponding to IEC 60034) and API 614, with exceptions and clarifications
    23. Electric generator surface treatment: ISO 12944-2:1998
    24. Main gear and couplings: AGMA 6011-I03
    25. Speed reduction gear: design according to AGMA 421
    26. Gas detection system: IEC/EN 60079-1:2004 explosion group IIC (zone 1)
    27. Fire extinguishing equipment: NFPA 12 with exceptions and clarifications
    28. CO2 bottles: European directive 1999/36/EC
    29. Motor control center: EN 60439 (corresponding to IEC 60439)
    30. Control system: EN 60439 (corresponding to IEC 60439)
    31. Frequency converters: EN 60204 (corresponding to IEC 60204)
    32. Electrical installation: EN 60204 (corresponding to IEC 60204)
    33. Control cables: EN 60204 (corresponding to IEC 60204)
    34. Power cables: EN 60204 (corresponding to IEC 60204)
    35. Factory tests: ISO 3977-8
    36. Customer documentation: ISO 5457-1999 with designation system KKS, documents structuring principles based on IEC 81346
  5. Abbreviations
    1. AN: air natural
    2. CEMS: continuous emission monitoring system
    3. CMS: condition monitoring system
    4. DC: data collector
    5. DCS: distributed control system
    6. DLE: dry low emission
    7. EPA: efficient particulate air filter (E10–E12)
    8. GG: gas generator
    9. HMI: human machine interface
    10. HART: highway addressable remote transducer
    11. HRSG: heat recovery steam generator
    12. I&C: instrument and control system
    13. LV: low voltage
    14. MCC: motor control center
    15. MCCB: molded case circuit breaker
    16. ONAN: oil natural air natural
    17. P&ID: process and instrument diagrams
    18. PT: power turbine
    19. RTD: resistance temperature device
    20. SFC: static frequency converter
    21. SIL: safety integrity level
    22. UCP: unit control panel
    23. UMD: uninterruptable motor drive
    24. UPS: uninterruptible power supply
  6. Gas Turbine Equipment
    1. Single shaft industrial type gas turbine with modular design, vertically split compressor casing for ease of maintenance
    2. Compressor inlet casing and inlet bellmouth casing
    3. All bearings of tilting pad type with directed mineral oil lubrication
    4. Thrust bearing #1 combined with radial journal bearing #1, located in inlet bellmouth casing
    5. Radial journal bearing #2, located in the turbine exhaust diffuser casing
    6. Two pneumatically actuated bleed valves for air bleed during startup and shutdown
    7. Ignition system including one removable high energy spark plug for startup burner
    8. Annular combustion chamber with internal thermal barrier coating
    9. Two optical flame detectors: one indicating flame at startup burner at ignition, one indicating cross ignition at startup; during operation both used as main flame detector
    10. 30 DLE burners of third generation for dual fuel
    11. Four fuel manifolds: two pilots, one central and one main
    12. Manually operated drain valves at compressor inlet plenum and bleed cavities and at combustion chamber and exhaust casings
    13. Turbine exhaust casing and exhaust diffuser
    14. Online combustor pulsation monitoring system with three dynamic pressure transducers continuously measuring combustor dynamic pressure
    15. Insulation of gas turbine and exhaust casing for personnel safety and heat and noise attenuation
    16. Dehumidifier unit for use in non-hazardous area, for engine dry out during extended shutdown periods
    17. 12 x 1.5 mm instrument tubing in 316L stainless steel with double ferrule couplings for core engine
    18. Instruments with trip function during operation: 2oo3 for gas turbine inlet and outlet pressure, axial displacement, exhaust gas temperature; 2oo3 for rotating speed; 1oo2 for flame detection
  7. Combustion Air Inlet System
    1. Air inlet system including weather protection, filters and silencer
    2. Filter house with service platform and ladder
    3. Single side pulse clean filter system with two filter stages: class F7 pulse filters as first stage, static class E10 disposable high efficiency filters as second stage
    4. Droplet separator as weather protection
    5. Support structure for filter house
    6. Hand operated hoist for filter replacement
    7. Air intake prepared for future chiller coil installation (chiller coils not included)
    8. Low pressure drop inlet silencer with baffles in 316L stainless steel
    9. Inlet plenum with inspection window
  8. Exhaust Gas System
    1. Exhaust gas system included