Caterpillar, XQ2000, 2000, 2000 eKW, 50/60 Hz, 3516B Engine, 40ft Container

Description

  1. Overview
    1. Caterpillar model XQ2000 generator sets
    2. Year models 2000 to 2004
    3. 5000 hours operation since new to rebuilt engines with 3k-to-5k hours
    4. Used condition
  2. Generator Set Features
    1. Factory designed, certified prototype tested with torsional analysis
    2. Production tested and delivered ready to connect to fuel and power lines
    3. Electric power design pro computer sizing available
    4. Supported 100% by your Caterpillar dealer with warranty on parts and labor
    5. Extended warranty available in some areas
    6. Designed and manufactured in an ISO 9001 compliant facility
    7. Meets or exceeds specifications: AS1359, AS2789, ABGSM TM3, BS4999, DIN6271, DIN6280, EGSA101P, JEM1359, IEC 34/1, ISO3046/1, ISO8528, NEMA MG1-22
  3. Caterpillar SR4B Generator
    1. Single bearing, wye connected, static regulated, brushless permanent magnet excited generator
    2. Designed to match the performance and output characteristics of the Caterpillar diesel engine that drives it
  4. Engine
    1. Reliable, fuel efficient diesel engine
    2. Compact, four-stroke-cycle diesel engine combines durability with minimum weight
    3. Fuel system operates on a variety of fuels
  5. Cooling System
    1. Sized compatible to rating with energy efficient fan and core
  6. Switchgear
    1. Single unit or optional paralleling components
    2. Circuit breakers, bus bars, and connection panel ready to connect
  7. Voltage Regulator
    1. Exclusive Caterpillar voltage regulator
    2. Three-phase sensing and adjustable volts-per-hertz regulation give precise control, excellent block loading, and constant voltage in the normal operating range
  8. Sound Attenuated ISO Container
    1. For ease of transportation and protection
    2. Meets 70 dBA at 50 ft or below per SAE J1074 measurement procedure
  9. Generator Specifications
    1. SR4B brushless, 480 volt, PM excited three-phase with digital voltage regulator, space heater
  10. Technical Data
    1. Power rating 60 Hz ekW: standby 2000, prime 1825
    2. Engine model: 3516B
    3. Container size: 12 m (40 ft)
    4. Container dimensions: 12 m (40 ft)
    5. Fuel capacity: 4732 L (1250 gal) standard
    6. Hours of operation at 60% load factor: standby 8 hours, prime 9 hours
    7. Approximate weight (dry) including container: 32,660 kg (72,000 lb)
    8. Approximate weight (dry) with undercarriage: 40,370 kg (89,000 lb)
  11. Standard Controls
    1. 12 m (40 ft) containers
    2. 480V/60 Hz
    3. Floorstanding switchgear includes the following functions and features
  12. Electronic Modular Control Panel (EMCP II) Components
    1. Generator set control (GSC)
    2. Monitoring: sequentially rotating, backlit LCD display of engine hours, engine RPM, DC battery voltage, oil pressure, and water temperature; includes pushbutton to hold display on any single parameter
    3. Protection: shutdowns for overspeed, overcrank, high water temperature, low oil pressure, and emergency stop with LED indicator for each condition
    4. Alarms: low coolant level
    5. AC metering: three-phase volts (L-L), amperes and frequency with phase select pushbutton on backlit LCD; metering accuracy is 0.5%
    6. Control: automatic starting with field adjustable cycle crank, failure to start (overcrank), and cooldown timer
    7. Programming and diagnostics: includes field programmable set-points for engine control and monitoring variables and self diagnosis of EMCP II system component and wiring failures
  13. Alarm Module
    1. Flashing LED warnings for: low coolant temperature, high coolant temperature (pre-alarm), low oil pressure (pre-alarm), engine control switch not in automatic, and low DC voltage
    2. Includes alarm horn and acknowledge pushbutton
  14. Engine Control Switch
    1. Snap action rotary switch, four-position: off/reset, automatic, manual, stop/cooldown
    2. Off/reset for engine shutdown and resetting faults
    3. Automatic for remote starting by customer contact closure
    4. Manual for local starting and manual paralleling
    5. Stop/cooldown for manual operation cooldown
  15. Alarm Acknowledge/Lamp Test Switch
    1. Three-position, spring return to center switch for alarm acknowledge and lamp test of all discrete indicating lamps
    2. Lamp test shall also sound the alarm horn
  16. Annunciation Circuits
    1. Upon receipt of an alarm or shutdown condition, the horn shall sound and an LED shall flash
    2. Upon acknowledgement from alarm acknowledge/lamp test switch, the horn shall be silenced and the lamp steadied
    3. LED shall be extinguished when ECS is placed in the off/reset position if the alarm condition has been corrected
    4. Circuits are recurring such that the LED shall flash and the horn sound, should another fault occur even prior to correction of the initial fault
  17. Emergency Stop Pushbutton
    1. Mushroom head, twist to reset, causes engine shutdown and tripping of the generator circuit breaker
    2. Prevents engine starting when depressed
  18. Manual Paralleling
    1. Controls consisting of reverse power relay, synchronizing lights, and switch
    2. Reverse power condition causes tripping of the generator circuit breaker, immediate engine shutdown, flashing of indicating lamp, and sounding of alarm horn
  19. Circuit Breaker
    1. Fixed mounted, three-pole, manually operated, molded case circuit breaker with solid state trip unit for overload (time overcurrent) and fault (instantaneous) protection
    2. Includes DC shunt trip coil activated on any generator set monitored fault
    3. Circuit breaker is sized for full load capacity of the generator set at 0.8 power factor
  20. Load Share Governor
    1. Electronic load sharing governor with speed adjust potentiometer, idle/rated switch, and isochronous/droop switch
  21. Voltage Regulator (Switchgear Mounted)
    1. Standard Caterpillar generator-mounted digital voltage regulator with voltage adjust rheostat mounted in the floorstanding switchgear
  22. Current Transformers
    1. Three five-ampere secondary with shorting terminal strips
  23. Potential Transformers
    1. Three 120 VAC secondary with primary and secondary fuse protection
    2. Two connected to the generator side of the circuit breaker, one connected to the load side of the circuit breaker
  24. Bus Bars
    1. Three-phase plus fully rated neutral bus bars with NEMA standard hole pattern for connection of customer load cables and generator cables
    2. Bus bars are sized for full load capacity of the generator set at 0.8 power factor
    3. Includes ground bus, connected to the generator frame ground and container frame with holes for connection of field ground cable
    4. Bus bars are accessible from outside of the power module via hinged, lockable cable access door
  25. Accessory Power
    1. 3500 power modules
    2. Three 230 VAC (50 Hz units) or 120 VAC (60 Hz units) shore power connections for jacket water heaters, generator space heater, and battery charger
  26. Battery Charger
    1. 24 VDC/20A battery charger with float/equalize modes and charging ammeter
  27. Specifications
    1. Hours of operation: 5000 hours since new / 3000 to 5000 hours on rebuilt engines