Caterpillar, 3516E, 2024, 24 MW Diesel Generator Set, 60Hz, 480V

Description

  1. Overview
    1. Caterpillar 3516 E new surplus
    2. Year 2024
    3. 3,000kW ea 480V 60Hz
    4. Caterpillar 3516E High Power Density (HPD) diesel generator sets
  2. Condition and Availability
    1. Unused, still wrapped under shrink wrap, open skid
    2. Ready to move within the US
    3. Full 1 year warranty from Caterpillar
  3. Engine Specifications
    1. Bore - mm (in): 170 (6.69)
    2. Stroke - mm (in): 215 (8.46)
    3. Displacement - L (in3): 78.1 (4766)
    4. Compression ratio: 13.9:1
    5. Aspiration: TA
    6. Fuel system: MEUI
    7. Governor type: ADEM™ A5
  4. Power Ratings
    1. Standby 60 Hz ekW (kVA): 3000 (3750)
    2. Mission critical 60 Hz ekW (kVA): 3000 (3750)
    3. Prime 60 Hz ekW (kVA): 2725 (3406)
    4. Emissions performance: U.S. EPA certified for emergency stationary applications (Tier 2)
  5. Features
    1. Caterpillar diesel engine
    2. Meets U.S. EPA stationary emergency use only (Tier 2) emissions standards
    3. Reliable performance proven in thousands of applications worldwide
    4. Certified alternative fuels including hydrotreated vegetable oil (HVO), renewable diesel (RD) and hydrotreated renewable diesel (HRD) which meet EN 15940 or ASTM D975 can be used or blended with EN 590 diesel
  6. Generator Set Package
    1. Accepts 100% block load in one step
    2. Meets NFPA 110 loading requirements
    3. Conforms to ISO 8528-5 G3 load acceptance requirements
    4. Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing
  7. Alternators
    1. Superior motor starting capability minimizes need for oversizing generator
    2. Designed to match performance and output characteristics of Caterpillar diesel engines
  8. Cooling System
    1. Cooling systems available to operate in ambient temperatures up to 50°C (122°F)
    2. Tested to ensure proper generator set cooling
  9. Caterpillar Energy Control System (ECS)
    1. User-friendly interface and navigation
    2. Scalable system to meet a wide range of installation requirements
    3. Expansion modules and site specific programming for specific customer requirements
    4. Graphical touchscreen display
    5. Easily upgradeable
  10. Warranty
    1. 24 months/1000-hour warranty for standby and mission critical ratings
    2. Extended service protection is available to provide extended coverage options
  11. Worldwide Product Support
    1. Caterpillar dealers have over 1,800 dealer branch stores operating in 200 countries
    2. Your local Caterpillar dealer provides extensive post-sale support, including maintenance and repair agreements
  12. Package Performance
    1. Engine speed: 1800 rpm
    2. Frequency: 60 Hz
    3. Gen set power rating with fan: 2725 to 3000 ekW
    4. Gen set power rating with fan @0.8 power factor: 3406 to 3750 kVA
    5. Emissions: Tier 2 (EPA ESE)
  13. Weights and Dimensions
    1. Rating ekW (kVA) 3000 (3750)
    2. Dim “A” mm (in) 7678 (302.3)
    3. Dim “B” mm (in) 2874 (113.2)
    4. Dim “C” mm (in) 3639 (143.3)
    5. Dry weight kg (lb) 20,380 (44,930)
  14. Ratings Definitions - Standby
    1. Output available with varying load for the duration of the interruption of the normal. Average power output is 70% of the standby rated ekW. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
  15. Ratings Definitions - Mission Critical
    1. Output available with varying load for the duration of the interruption of the normal. Average power output is 85% of the mission critical rated ekW. Typical peak demand up to 100% of rated ekW for up to 5% of the operating time. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
  16. Ratings Definitions - Prime
    1. Output available with varying load for an unlimited time. Average power output is 70% of the prime rated ekW. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year.
  17. Applicable Codes and Standards
    1. AS 1359, ULC 2200 3rd edition, UL 489, UL 869A, IBC, IEC 60034-1, ISO 3046, ISO 8528, NEMA MG1-22, NEMA MG1-33, 2014/35/EU, 2006/42/EC, 2014/30/EU and facilitates compliance to NFPA 37, NFPA 70, NFPA 99, NFPA 110.