Hurst, S45-G-207.5, 2016, 207.5 HP, 60 PSI, Natural Gas Fired

Description

  1. Overview
    1. Condition: new, never used
    2. Built new in 2016; complete, never installed and ready to delivery
    3. Actual model is: Hurst S45-G-207.5-60W
  2. Specifications
    1. Series 45: 207.5 hp; 60 psi hot water; natural gas fired firebox
    2. Efficient 3-pass design natural gas fired firebox
    3. Asme code constructed and stamped for 15 psi steam; 30 - 100 psi water
    4. Registered with the national board of boiler inspectors
    5. Boiler design: 3-pass "firebox" design with stress relieving "wetback" firetube construction
    6. Hot water pressures models are from: 8.5 - 415 hp; 100 psi max.; 500 - 813 hp; 60 psi max. Built to section-IV asme code
    7. Hot water temperature not to exceed 250 degrees f at or near the outlet of boiler
    8. Fireside heating surface: 830 sq/ft. Furnace volume: 132 cu/ft
    9. Hot water outlet: 8"; hot water drain: 6"; drain connection: 2"
  3. Electrical / Voltage
    1. 480 v, 60 cy, 3 ph
  4. Construction Features
    1. Unified refractory base floor; steel skids; lifting eyes
    2. Low heat release; factory insulated - 2" mineral wool, factory jacketed and painted
    3. Easy access to fireside surfaces; ample waterside clean-out openings
    4. Wet back construction
    5. High density 2" mineral wool insulation assures lower radiant heat loss
  5. Controls and Operation
    1. Fully automatic operation; u.l. listed; forced draft burners
    2. U.l. listed controls and trim
    3. Factory test fired, flame observation ports front and rear
    4. Hot water model tim: safety relief valve; operating temperature control; high limit temperature control with manual reset; combination pressure and temperature gauge; low water cutoff control with manual reset
    5. Hot water supply: 180 dif return: 160 dif
  6. Burner and Fuel System
    1. Burner: matched ul listed "forced draft" power burners with factory pre-piped, wired and tested fuel configurations for natural gas, propane (lp) gas, no. 2 (diesel) oil, or combination of both gas/oil
    2. All units are factory packaged with operating controls, relief valves, burner, and fuel train. Installation is made simple in that only service connections are needed to place in operation
    3. In addition to meeting the requirements of u.l., burner systems are optionally available to meet the requirements of fm, iri, military, and others