MTU, DL3300, New, 2400kW, 6.6kV, 50Hz, Diesel Generator Set (New)

Description

  1. Overview

    1. Item 001: Mtu diesel gensets – new

    2. Item 002: Paralleling cabinet – quantity 4

    3. Item 003: High voltage switchgear – quantity 4

    4. Item 004: Pt unit – quantity 1

  2. Genset Specifications

    1. Model of generating sets: Dl3300

    2. Rated power: 2400 kW

    3. Standby power: 2640 kW

    4. Rated voltage: 6.6 kV

    5. Rated current: 275 A

    6. Rated frequency: 50 Hz

    7. Rated speed: 1500 rpm

    8. Rated power factor: 0.8 (lag)

    9. Supply method: 3 phases 4 lines

    10. Cooling system: Closed cycle water-cooled with fan, cooling radiator

    11. Reference overall dimension (L x W x H): 7600 x 2200 x 2400 mm

    12. Reference dry weight: 19000 kg

    13. Excitation method: Brushless, self-excitation

  3. Engine Specifications

    1. Model of engine: Mtu 20V4000G63LF

    2. Rated power: 2590 kW

    3. Number of cylinders: 20

    4. Induction system: Turbocharged and air charge cooled

    5. Combustion system: Direct injection

    6. Rated speed: 1500 rpm

    7. Speed modulate method: Electronic governor

    8. Starting method: 24V dc starter

  4. Alternator Specifications

    1. Alternator model: Engga EG630GSD 506600

    2. Rated capacity: 2500 kW

    3. Rated voltage: 6.6 kV

    4. Rated current: 275 A

    5. Rated speed: 1500 rpm

    6. Rated frequency: 50 Hz

    7. Rated power factor: 0.8 (lag)

    8. Insulation grade: Class H

    9. Level of protection: IP23

    10. Mode of connection: Three phases, four wires

    11. Voltage regulating mode: Avr

    12. Excitation method: Brushless self-excitation (pmg)

    13. Cooling mode: Air natural cooling

    14. Working mode: Continuous duty

  5. Control Panel

    1. Brand protection: Deepsea

    2. Display: Lcd (132 x 64)

    3. Controller language: German & English & Spanish & Russian & others

  6. Alarm Functions

    1. Speed is too high/too low

    2. The battery voltage is too low or too high

    3. Start and stop failed

    4. Charging failure

    5. Over-current

    6. Unit voltage is too low/too high

    7. Low oil pressure

    8. Emergency stop

    9. Excessive engine temperature

    10. Overload

  7. Monitor Display

    1. Unit voltage (phase-phase/phase-line)

    2. Engine oil pressure (pounds per square inch - bar)

    3. Current (L1, L2, L3)

    4. Engine temperature (°C and °F)

    5. Unit frequency (Hz)

    6. Factory battery voltage

    7. Engine running hour meter

    8. Unit kva, kwh

    9. Unit power as a percentage of rated power

    10. Unit cos

  8. Voltage Regulation

    1. Stable regulating rate: ±2.5%

    2. Instantaneous regulating rate: ≤±20%

    3. Recovery time: ≤2 s

    4. Fluctuation: ≤1%

  9. Frequency Regulation

    1. Stable regulating rate: 0–5%

    2. Instantaneous regulating rate: ≤±10%

    3. Recovery time: 7 s

    4. Fluctuation: ≤1%

  10. Included Components

    1. 1 engine Mtu 20V4000G63LF – 1 unit

    2. 2 alternator Engga EG630GSD 506600 – 1 unit

    3. 3 coupler high elastic rubber coupling, connecting engine and generator – 1 unit

    4. 4 switchgear high voltage switchgear – 1 unit

    5. 5 common chassis channel steel chassis – 1 unit

    6. 6 cooling system closed cycle water-cooled with fan, cooling radiator – 1 unit

    7. 7 control panel Deepsea – 1 unit

    8. 8 exhaust pipe and silencer industrial silencer – 1 unit

    9. 9 breaker Chint – 1 unit

    10. 10 charger constant potential battery charger – 1 unit

    11. 11 storage battery lead acid maintenance-free battery – 1 unit

    12. 12 battery cable pure copper battery wire – 1 unit

    13. 13 absorber bowl shape weighted rubber shock absorber – 1 unit

    14. 14 technical document standard – 1 unit

    15. 15 random tools and spare parts standard – 1 unit