Caterpillar, 3516E, 2023, Diesel Generator Set, 3,250 kVA / 2,600 kW Standby, 400 V, 50 Hz

Description

New as presented to American Plant and Equipment by the seller.

  1. Overview
    1. Make and model: Caterpillar 3516E diesel generator set, 50 Hz
    2. Year: 2023
    3. Quantity available: 10 units
    4. Total output of the 10 units: 32.5 MVA / 26 MW standby
    5. Duty cycles: standby, mission critical and prime
  2. Condition
    1. New and never used, 0 operating hours
    2. Never commissioned, installed or operated
  3. Ratings and Output (per unit)
    1. Standby rating: 3,250 kVA / 2,600 kW (3,487 hp) at 0.8 power factor
    2. Prime rating: 2,950 kVA
    3. Output: 400 V, three phase, 50 Hz, 1500 rpm
    4. Rated current: 4,691 A
    5. Generator connection: wye, 6 lead; insulation class H; generator frame 1868E
    6. Emissions: Tier 2 equivalent, US EPA stationary emergency / low NOx (1/2 TA Luft)
  4. Engine
    1. Caterpillar 3516E, V-16, 4-stroke, water-cooled diesel
    2. Bore x stroke: 170 mm (6.7 in) x 215 mm (8.5 in)
    3. Displacement: 78.1 liters (4,766 cu in)
    4. Compression ratio: 14.0:1
    5. Aspiration: ATAAC (turbocharged, air-to-air aftercooled)
    6. Fuel system: electronic unit injection
    7. Governor and engine control: Cat ADEM A5
  5. Fuel Consumption (3,250 kVA standby rating, with fan)
    1. 100% load: 692.0 L/hr (182.8 gal/hr)
    2. 75% load: 538.5 L/hr (142.3 gal/hr)
    3. 50% load: 370.4 L/hr (97.8 gal/hr)
    4. 25% load: 206.9 L/hr (54.7 gal/hr)
  6. Dimensions and Weight
    1. Length: about 7,685 to 7,785 mm (302.6 to 306.5 in)
    2. Dry weight: up to about 20,707 kg (45,650 lb) per unit
  7. Performance
    1. Designed to ISO 8528-5 steady-state and transient response requirements
    2. Accepts 100% rated load in one step
    3. Meets NFPA 110 loading requirements
    4. Full rated power up to 50 C (122 F) ambient
  8. Control System
    1. Cat EMCP 4 series digital controller with Modbus RTU customer data link
    2. Protective functions include reverse power (32), reverse reactive power (32RV), overcurrent (50/51), over and under voltage (27/59) and over and under frequency (81 o/u)
    3. Full metering: volts, amps, kW, kVA, kVAr, power factor, frequency, kW-hr and kVAr-hr totals, oil pressure, coolant temperature and operating hours
  9. Factory Quality and Documentation
    1. Each generator set fully assembled and tested at a Caterpillar facility before dispatch
    2. Factory load-test reports available for each unit
    3. Caterpillar operation and maintenance manuals
  10. Packaging
    1. Most units in their original factory packaging
    2. The remaining units prepared in containers, ready for transport