NovaStar, GL440, Resistive Load Bank, 1,500 kW, 480/240 V, 60 Hz (New)

Description

  1. Overview

    1. Dual-voltage rated performance: 480 Vac series and 240 Vac parallel

    2. Rated power 1500 kW (2,011.5 hp) in both voltage modes

    3. Line current 3608 / 1804 A at 240 / 480 V

    4. Load control from 0 to 1500 kW (2,011.5 hp) in 1 kW (1.3 hp) steps

    5. PLC combines 16 load stages

    6. Three-phase, 60 Hz

  2. Applications

    1. Genset load test

    2. UPS load test

    3. Power grid balancing

    4. Data center server load simulation

    5. BESS test

  3. Key Features

    1. High accuracy load testing

    2. Side airflow design for flexible installation

    3. Industrial-grade resistive elements

    4. Smart control system with local and remote operation

    5. Comprehensive safety protection

    6. Robust and customizable design

  4. Electrical Specifications

    1. 480 Vac series mode: 1500 kW (2,011.5 hp)

    2. 240 Vac parallel mode: 1500 kW (2,011.5 hp)

    3. Line current 3608 / 1804 A at 240 / 480 V

    4. Load switching by 3-pole contactors

    5. Each stage uses interlocked series/parallel contactor groups and branch fuses

    6. 480 V selects series; 240 V selects parallel

    7. Both modes deliver the same rated stage power

    8. Main load connection via tin-plated copper busbars

    9. Busbar system configured for 240 Vac full-load current of approximately 3608 A

    10. Resistive elements: finned stainless-steel tubular elements with nickel-chromium resistance cores

  5. Control And Monitoring

    1. Local control via HMI touch screen

    2. Remote control via PC-based software

    3. Interface: RJ45

    4. Communication type: Modbus TCP

    5. Digital meter: V/A/kW/Hz/Pf

    6. Local HMI touchscreen with status indicators and manual controls

    7. SA-M selects the main voltage mode; switching under load is prohibited

    8. SA-A selects the auxiliary supply voltage; SA-A and SA-M are independent

    9. Only the selected control mode can load; a mode change clears load commands

  6. Auxiliary Supply

    1. External 240/480 Vac, 60 Hz feeds isolating transformer TF0 through selector SA-A

    2. TF0 supplies 480 V fans and 230 V controls

    3. PS1 supplies 24 VDC electronics

    4. Protected external 240/480 Vac input feeds TF0 through an off-load voltage selector

    5. TF0 isolates and converts to 480 Vac / 60 Hz

    6. Primary, secondary and control branches are protected

    7. TF0 neutral N2 is bonded to PE once at its origin; main N is separate

  7. Cooling And Airflow

    1. Air direction: horizontal

    2. Quantity of fans: 4 × 4.5 kW (6 hp)

    3. Fans operate at 480 Vac / 60 Hz from TF0

    4. Each fan has an independent contactor, overload protection and airflow-pressure switch

    5. Air volume: 70 m³ per kW per hour (2,472 ft³ per kW per hour)

    6. 304 stainless-steel louvers and protective mesh fitted at the hot-air exhaust side

    7. Keep fans running for at least 5 minutes after removing load before normal shutdown

  8. Protections

    1. Fans overload protection

    2. Fans low air volume protection

    3. Overtemperature cut-out: 120 °C (248 °F)

    4. Auxiliary circuit MCB

    5. Local/remote control mode inter-lock

    6. Any fan airflow or overload fault, 120 °C (248 °F) trip or voltage-mode mismatch unloads all stages

    7. Break-before-make interlocks exclude both voltage modes

  9. Enclosure Structure

    1. Enclosure type: cabinet

    2. Noise level: 85 ±3 dB(A)

    3. Size (W × D × cabinet H): 2800 × 1726 × 2060 mm (110.2 × 68.0 × 81.1 in)

    4. Depth includes the control cabinet; height excludes lifting eyes

    5. Weight: 2500 kg (5,512 lb)

    6. Portability: lifting eyes and forklift pockets

    7. IP grade of control chamber: IP54

    8. IP grade of complete enclosure: IP2X

    9. Control cabinet: 702 mm (27.6 in) wide × 276 mm (10.9 in) projection

    10. Control-box lower edge: 610 mm (24.0 in)

  10. Operating Conditions

    1. Temperature: -20 °C to +50 °C (-4 °F to 122 °F)

    2. Altitude: up to 2000 m (6,562 ft) above sea level

  11. Operating Sequence

    1. Connect: with both supplies isolated, connect main L1/L2/L3/N, external auxiliary L1/L2/L3 and PE; match SA-M to main voltage and SA-A to auxiliary voltage before energizing

    2. Start cooling: energize auxiliary power, confirm TF0 output and start all four 480 V / 60 Hz fans; confirm normal airflow and no active fault

    3. Apply load: confirm voltage-mode match and all load contactors open; select Local or Remote, release RESET/LOAD, reset manually, then issue a new LOAD command

    4. Monitor: monitor readings and alarms; before voltage-mode changes, unload, prove all contactors open and isolate the relevant supply

    5. Unload and cool: remove the load, then keep the fans running for at least 5 minutes before normal shutdown

    6. Reset after a trip: clear the fault, release RESET and LOAD, reset manually, then issue a fresh LOAD command

  12. Connection Points

    1. Mains power cable entry

    2. Auxiliary power entry

    3. RJ45 connection

    4. Air intake louvers

    5. Air exhaust louvers

  13. Spare Parts Supplied

    1. Intermediate relays: 4 units

    2. Branch load fuses: 3 units

    3. Air-pressure switches: 2 units

    4. Ni-Cr heating elements (resistors): 3 to 6 units

    5. Indicators and push buttons: 2 units