Description
Overview
Dual-voltage rated performance: 480 Vac series and 240 Vac parallel
Rated power 1500 kW (2,011.5 hp) in both voltage modes
Line current 3608 / 1804 A at 240 / 480 V
Load control from 0 to 1500 kW (2,011.5 hp) in 1 kW (1.3 hp) steps
PLC combines 16 load stages
Three-phase, 60 Hz
Applications
Genset load test
UPS load test
Power grid balancing
Data center server load simulation
BESS test
Key Features
High accuracy load testing
Side airflow design for flexible installation
Industrial-grade resistive elements
Smart control system with local and remote operation
Comprehensive safety protection
Robust and customizable design
Electrical Specifications
480 Vac series mode: 1500 kW (2,011.5 hp)
240 Vac parallel mode: 1500 kW (2,011.5 hp)
Line current 3608 / 1804 A at 240 / 480 V
Load switching by 3-pole contactors
Each stage uses interlocked series/parallel contactor groups and branch fuses
480 V selects series; 240 V selects parallel
Both modes deliver the same rated stage power
Main load connection via tin-plated copper busbars
Busbar system configured for 240 Vac full-load current of approximately 3608 A
Resistive elements: finned stainless-steel tubular elements with nickel-chromium resistance cores
Control And Monitoring
Local control via HMI touch screen
Remote control via PC-based software
Interface: RJ45
Communication type: Modbus TCP
Digital meter: V/A/kW/Hz/Pf
Local HMI touchscreen with status indicators and manual controls
SA-M selects the main voltage mode; switching under load is prohibited
SA-A selects the auxiliary supply voltage; SA-A and SA-M are independent
Only the selected control mode can load; a mode change clears load commands
Auxiliary Supply
External 240/480 Vac, 60 Hz feeds isolating transformer TF0 through selector SA-A
TF0 supplies 480 V fans and 230 V controls
PS1 supplies 24 VDC electronics
Protected external 240/480 Vac input feeds TF0 through an off-load voltage selector
TF0 isolates and converts to 480 Vac / 60 Hz
Primary, secondary and control branches are protected
TF0 neutral N2 is bonded to PE once at its origin; main N is separate
Cooling And Airflow
Air direction: horizontal
Quantity of fans: 4 × 4.5 kW (6 hp)
Fans operate at 480 Vac / 60 Hz from TF0
Each fan has an independent contactor, overload protection and airflow-pressure switch
Air volume: 70 m³ per kW per hour (2,472 ft³ per kW per hour)
304 stainless-steel louvers and protective mesh fitted at the hot-air exhaust side
Keep fans running for at least 5 minutes after removing load before normal shutdown
Protections
Fans overload protection
Fans low air volume protection
Overtemperature cut-out: 120 °C (248 °F)
Auxiliary circuit MCB
Local/remote control mode inter-lock
Any fan airflow or overload fault, 120 °C (248 °F) trip or voltage-mode mismatch unloads all stages
Break-before-make interlocks exclude both voltage modes
Enclosure Structure
Enclosure type: cabinet
Noise level: 85 ±3 dB(A)
Size (W × D × cabinet H): 2800 × 1726 × 2060 mm (110.2 × 68.0 × 81.1 in)
Depth includes the control cabinet; height excludes lifting eyes
Weight: 2500 kg (5,512 lb)
Portability: lifting eyes and forklift pockets
IP grade of control chamber: IP54
IP grade of complete enclosure: IP2X
Control cabinet: 702 mm (27.6 in) wide × 276 mm (10.9 in) projection
Control-box lower edge: 610 mm (24.0 in)
Operating Conditions
Temperature: -20 °C to +50 °C (-4 °F to 122 °F)
Altitude: up to 2000 m (6,562 ft) above sea level
Operating Sequence
Connect: with both supplies isolated, connect main L1/L2/L3/N, external auxiliary L1/L2/L3 and PE; match SA-M to main voltage and SA-A to auxiliary voltage before energizing
Start cooling: energize auxiliary power, confirm TF0 output and start all four 480 V / 60 Hz fans; confirm normal airflow and no active fault
Apply load: confirm voltage-mode match and all load contactors open; select Local or Remote, release RESET/LOAD, reset manually, then issue a new LOAD command
Monitor: monitor readings and alarms; before voltage-mode changes, unload, prove all contactors open and isolate the relevant supply
Unload and cool: remove the load, then keep the fans running for at least 5 minutes before normal shutdown
Reset after a trip: clear the fault, release RESET and LOAD, reset manually, then issue a fresh LOAD command
Connection Points
Mains power cable entry
Auxiliary power entry
RJ45 connection
Air intake louvers
Air exhaust louvers
Spare Parts Supplied
Intermediate relays: 4 units
Branch load fuses: 3 units
Air-pressure switches: 2 units
Ni-Cr heating elements (resistors): 3 to 6 units
Indicators and push buttons: 2 units