STX-Niigata, 8L22HLX, 1.7MW, 50Hz, HFO Containerized Power Plant (New)

Description

  1. Overview
    1. Brand new HFO CPP (containerized power plant).
    2. In the past, the containerized generator market was mainly based on DO (diesel oil). In the majority of DO power solutions, the largest component of the total cost to generate energy is the fuel. Now, HFO CPP will be a great solution to reduce operating costs and maximize customer benefit.
  2. Engine Specifications
    1. Engine model: STX-Niigata 8L22HLX.
    2. Engine output: 1760 kWm.
    3. Generator output: 1680 kWe.
    4. Gen-set dimension (L x W x H): 8019 x 1977 x 2834 mm.
    5. Bore x stroke: 220 x 300 mm.
    6. Engine speed: 900 / 1000 rpm.
    7. Frequency: 60/50 Hz.
    8. Output per cylinder: 220 / 220 kW.
    9. BMEP: 25.7 / 23.2 bar.
    10. SFOC1): 186 g/kWmh + 5% tolerance.
    11. LO consumption: 0.5 g/kWmh + 20% tolerance.
    12. Emission: WB 2007/8.
    13. Fuel: DO / HFO / crude oil.
    14. 1) Under ISO 3046-1 conditions and excluding engine driven pump.
  3. Composition of Power Plant
    1. Entire items fully containerized.
  4. Features of Containerized Power Plant
    1. Fully containerized design.
    2. Quick and easy installation with few on-site piping and cabling works.
    3. Quick and easy commissioning as most equipment is checked in Korea.
    4. Quick and easy operation and maintenance with convenient O&M device and sufficient space.
  5. Comparative Advantage
    1. Containerizing: Entire items (fully containerized) vs. competitor excluding items (radiator, EG silencer, EG boiler and stack, ventilation system, etc.).
    2. Transportation: Container truck, bulk carrier, container ship (fully containerized) vs. competitor various truck, bulk carrier (not fully containerized).
    3. Installation: Quick and easy (few on-site piping and cabling works) vs. competitor more long and difficult (above excluding items should be installed at site).
    4. Commissioning: Quick and easy (most equipment should be checked in Korea) vs. competitor more long and difficult (proportional to the amount of on-site installation).
    5. O&M: Quick and easy (convenient O&M device and sufficient space) vs. competitor more long and difficult (insufficient space).
  6. Specifications
    1. Voltage: 13,800 V