C-3994 BARGEMOUNTED POWER PLANT, CAPACITY 220MW

C-3994 BARGEMOUNTED POWER PLANT, CAPACITY 220MW

A. ONCE THROUGH STEAM GENERATOR
B. BARGE
C. CHILLERS
D. AIR COMPRESSOR
E. GAS TURBINE
F. STEAM TURBINE
G. FEEDWATER SYSTEM
H. CLOSED COOLING WATER SYSTEM
I. AUXILIARY COOLING WATER SYSTEM
J. CONDENSATE POLISHING UNIT (CPU)
K. WASTE WATER SYSTEM
L. PLANT ELECTRICAL SYSTEM
M. BLACK START DG SET
N. PLANT CONTROLS AND INSTRUMENTATION
O. PLANT FIRE FIGHTING SYSTEM
P. START UP VACUUM SYSTEM
Q. STEAM TURBINE DEAERATING CONDENSER

QUANTITY: 1 PLANT

In stock
SKU
C-3994
Call Image
Call: +1 (864) 574-0404

We will send this product in 2 days. Read more...

Call us now for more info about our products.

Return purchased items and get all your money back.

Buy this product and earn 10 special loyalty points!


REFERENCE NUMBER: C-3994
BARGEMOUNTED POWER PLANT, CAPACITY 220MW

DETAILS:

OFFER 001
A. ONCE THROUGH STEAM GENERATOR
ONCE THROUGH STEAM GENERATORS ALSO CALLED OTSG ARE SUPPLIED BY IST, CANADA. THESE ARE THE STEAM GENERATORS, WHICH GENERATE STEAM FOR POWER GENERATION IN STEAM TURBINE. THE HEAT IN THE EXHAUST GASES FROM GAS TURBINES IS TRANSFERRED TO FEED WATER TO GENERATE STEAM AT TWO PRESSURES, HP & LP. THE OTSG ARE DRUM LESS BOILERS HAVING TUBE BUNDLES WHERE STEAM IS GENERATED. FEED WATER IS SUPPLIED TO OTSG THROUGH FEED WATER PUMPS AFTER TREATING THE WATER IN CONDENSATE POLISHING UNIT. SUPPLING DM WATER TO CONDENSER HOT WELL FULFILS THE ADDITIONAL MAKEUP REQUIREMENT. THE EXHAUST GASES AFTER GIVING THEIR HEAT TO FEED WATER ARE LET OFF TO ATMOSPHERE THROUGH STACK. THE OTSG HAS A DRY RUNNING CAPABILITY UP TO 560°C.

GENERAL SPECIFICATION:
MANUFACTURE: INNOVATIVE STEAM TECHNOLOGIES
TYPE: ONCE THROUGH STEAM GENERATOR
NUMBER OF BOILERS: 4
WORKING PR IN PSIG / KG/CM2 (G): HP - 865 / 59.62 &
LP - 68.3 / 4.71
DESIGN PR IN PSIG / KG/CM2 (G): HP - 953 / 65.71 &
LP - 103 / 7.10
HYDRAULIC TEST PRESSURE IN PSIG / KG/CM2 (G): HP - 1884 / 129.87 &
LP - 384 / 26.47
FLUE GASES: GAS TURBINE EXHAUST FLUE GAS
CAPACITY IN LB/HR / KG/HR.: HP - 107600/48806.5 &
LP - 35570/16134.28
DESIGN DRY RUNNING GAS TEMPERATURE: 986 F
MAXIMUM OPERATING GAS TEMPERATURE: 856 F

OFFER 002
B. BARGE
THE FUNCTION OF BARGE IS TO CONTAIN AND DELIVER 1(ONE) COMBINED CYCLE BARGE MOUNTED FLOATING POWER PLANT OF NOMINAL NET CAPACITY 220 MW, CONSISTING OF 4(FOUR) ONCE THROUGH STEAM GENERATOR (OSTG), 1(ONE) STEAM TURBINE GENERATOR (STG), 4(FOUR) COMBUSTION GAS TURBINE GENERATORS AND AUXILIARY EQUIPMENT CONDENSERS, CHILLING SYSTEM FOR AIR INTAKE AND THE REMAINING BALANCE OF PLANT. THE BASIC DESIGN IS TO INCLUDE THE BARGE AND THE CONNECTIONS TO THE MOORING SYSTEM, TOGETHER WITH THE POWER PLANT EQUIPMENT.

THE DESIGN DATA OF THE BARGE
A) BARGE SIZE (LENGTH X WIDE X DEPTH): 106M X 55.2M X 6M
B) BARGE DRAFT FOR TOWING: 2.4 M (NORMAL OPERATION 3.4M)
C) TOTAL BARGE WEIGHT: 13,900TONNES
(BARGE ITSELF INCLUDING STEAM TURBINE HALL, CONTROL BUILDING AND ABOVE DECK FOUNDATIONS: APPROXIMATE 6,000 TONNES)

STABILITY
A) THE BARGE IS DESIGNED TO COMPLY WITH THE INTACT STABILITY REGULATION OF US 46 CFR CHAPTER I, SECTION 174.015 FOR RIVER AND HARBOR SERVICE.
B) THE BARGE IS DESIGNED TO COMPLY WITH THE ONE COMPARTMENT DAMAGE STABILITY REGULATIONS OF US 46 CFR CHAPTER I, SECTION 172.065. THE BARGE SHALL COMPLY WITH A WIND HEELING MOMENT AS DEFINED IN CFR CHAPTER I, SECTION 174.055
C) THE BARGE IS DESIGNED TO COMPLY WITH IMO INTERNATIONAL CONVENTION ON LOAD LINES

BARGE ACCESS
FOUR (4) RAMPS ARE DESIGNED TO ACCESS THE BARGE FROM SHORE
ONE (1) MAIN RAMP 6M WIDE
ONE (1) RAMP 4.5M AND
TWO (2) AUXILIARY RAMPS 3.5M WIDE RESPECTIVELY

BARGE VENTILATION
BELOW DECK SPACES ARE VENTILATED ACCORDING TO THE RECOMMENDED PRACTICES OF SNAME T&R 4 TO 16” CALCULATION MERCHANT SHIP HEATING, VENTILATION AND AIR CONDITION DESIGN”.
FANS ARE SIZED TO LIMIT THE TEMPERATURE RISE IN THE VENTILATED SPACES TO BE LESS THAN 5OC AND TO PROVIDE SUFFICIENT VENTILATION AIR TO ENSURE NOXIOUS FUMES ARE BELOW ACCEPTED OCCUPATIONAL SAFETY REGULATION LEVELS.

OFFER 003
C. CHILLERS
CHILLERS ARE USED TO COOL GAS TURBINE INTAKE AIR AND ENHANCING THE OUTPUT OF EACH GAS TURBINE BY 7 TO 10 MW APPROXIMATELY. THE CHILLERS OPERATE ON VAPOUR COMPRESSION CYCLE. CHILLED WATER IS CIRCULATED THROUGH EVAPORATOR WHERE IT REJECTS HEAT TO REFRIGERANT HFC134A AND BECOME CHILLED. THIS CHILLED WATER AGAIN PICKS UP HEAT FROM GAS TURBINE INTAKE AIR-COOLING THEM. THE BOILED REFRIGERANT IS THAN COMPRESSOR. THE HEAT ADDED TO THE REFRIGERANT IN EVAPORATOR AND COMPRESSOR IS THAT REJECTED IN CONDENSER, COOLED BY SEA WATER. THE MOTOR IS HERMETICALLY SEALED. LUBE OIL AND MOTOR WINDINGS ARE COOLED BY REFRIGERANT. THEREFORE HEAT FROM A LOW TEMPERATURE SOURCE IS REJECTED TO HIGH TEMPERATURE SOURCE.

DESIGN CRITERIA
1) SITE CONDITION
GT CHILLER COIL REQUIRED COOLING CAPACITY: 1200 USRT X 2 SETS
2) GT CHILLER COOLING COIL DESIGN CONDITION
INLET AIR CONDITION (AMBIENT): 37 ° DB / 75 % RH
OUTLET AIR CONDITION (GT INLET AIR): 7.22 ° DB / 95 % RH
GT INLET AIR FLOW RATE: 128.9 KG/S
CHILLED WATER SUPPLY / RETURN TEMP: 5 ° C / 13.8 ° C
CHILLED WATER FLOW RATE: 326 M3 / H

CHILLED WATER SYSTEM CONSISTS WITH THE FOLLOWING EQUIPMENT:
GROUP 1
OFFER 003A
GT-1
NAME: COMBUSTION AIR CHILLING COIL #1
REMARKS: 100%
QUANTITY: 1 SET

OFFER 003B
GT-2
NAME: COMBUSTION AIR CHILLING COIL #2
REMARKS: 100%
QUANTITY: 1 SET

OFFER 003C
CS-M-CH01-1A
NAME: CENTRIFUGAL CHILLER #1A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003D
CS-M-CH01-1B
NAME: CENTRIFUGAL CHILLER #1B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003E
CS-M-CH01-2A
NAME: CENTRIFUGAL CHILLER #2A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003F
CS-M-CH01-2B
NAME: CENTRIFUGAL CHILLER #2B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003G
CS-M-PP01-1A
NAME: CHILLED WATER CIRCUL P/P #1A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003H
CS-M-PP01-1B
NAME: CHILLED WATER CIRCUL P/P #1B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003I
CS-M-PP01-2A
NAME: CHILLED WATER CIRCUL P/P #2A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003J
CS-M-PP01-2B
NAME: CHILLED WATER CIRCUL P/P #2B
REMARKS: 50%
QUANTITY: 1 SET

GROUP 2
OFFER 003K
GT-3
NAME: COMBUSTION AIR CHILLING COIL #3
REMARKS: 100%
QUANTITY: 1 SET

OFFER 003L
GT-4
NAME: COMBUSTION AIR CHILLING COIL #4
REMARKS: 100%
QUANTITY: 1 SET

OFFER 003M
CS-M-CH01-3A
NAME: CENTRIFUGAL CHILLER #3A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003N
CS-M-CH01-3B
NAME: CENTRIFUGAL CHILLER #3B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003O
CS-M-CH01-4A
NAME: CENTRIFUGAL CHILLER #4A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003P
CS-M-CH01-4B
NAME: CENTRIFUGAL CHILLER #4B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003Q
CS-M-PP01-3A
NAME: CHILLED WATER CIRCUL P/P #3A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003R
CS-M-PP01-3B
NAME: CHILLED WATER CIRCUL P/P #3B
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003S
CS-M-PP01-4A
NAME: CHILLED WATER CIRCUL P/P #4A
REMARKS: 50%
QUANTITY: 1 SET

OFFER 003T
CS-M-PP01-4B
NAME: CHILLED WATER CIRCUL P/P #4B
REMARKS: 50%
QUANTITY: 1 SET

DETAILS OF CHILLER:
NAME PLATE DETAILS:
TYPE: CENTRIFUGAL
MAKE: CARRIER, USA
REFRIGERANT USED: R 134A
QUANTITY OF REFRIGERANT CHARGE: 1270 KG
NO. OF CHILLERS: 8
CAPACITY: 1210 USRT EACH
MOTOR: HERMETICALLY SEALED
RATED POWER: 808 KW
DESIGN CHILLED WATER TEMPERATURE: 5°C
DELTA T ACROSS EVAPORATOR: 8.8°C
CHILLED WATER FLOW RATE: 415.77 M3/HR
DESIGN SEA WATER INLET TEMPERATURE: 29°C
DELTA T ACROSS CONDENSER: 6 °C
CONDENSER SEA WATER FLOW RATE: 739 M3/HR
NO OF TUBES IN EVAPORATOR: 976
EVAPORATOR TUBE DIAMETER: 19.05mm
EVAPORATOR HEAT TRANSFER AREA: 228 M2
EVAPORATOR TUBE MATERIAL: COPPER
CHILLED WATER: DM WATER
EVAPORATOR FOULING FACTOR: 0.00008806 M2.DEG.C/W
LMTD ACROSS EVAPORATOR: 7.13
EVAPORATOR APPROACH: > 1°C
NO OF TUBES IN CONDENSER: 1170
CONDENSER TUBE DIAMETER: 19.05mm
CONDENSER HEAT TRANSFER AREA: 257 M2
CONDENSER TUBE MATERIAL: TITANIUM

CONDENSER FOULING FACTOR: 0.00008806 M2.DEG.C/W
LMTD ACROSS EVAPORATOR: 3.08
CONDENSER APPROACH: 1 TO 2 ºC
COEFFICIENT OF PERFORMANCE (COP): 5.2
ENERGY EFFICIENCY: 0.192
MAIN MOTOR: 6,600 V, 50 HZ, AND 3 PH
AUX. POWER: 415 V, 50 HZ, 3 PH

OFFER 004
D. AIR COMPRESSOR
THE PLANT INSTRUMENT AIR AND SERVICE AIR REQUIREMENT ARE MET THROUGH SCREW TYPE AIR COMPRESSORS LOCATED IN BARGE BELOW DECK COMPARTMENTS. THERE ARE 3 X 100 % COMPRESSORS INSTALLED, HAVING ONE INSTRUMENT AIR RECEIVER AND ONE SERVICE AIR RECEIVER. THE INSTRUMENT AIR IS PASSES THROUGH 2 X 100 % DESICCANT TYPE DRYERS WHICH DRIES THE AIR FOR USE IN INSTRUMENTS. THE COMPRESSORS ARE WATER COOLED. TO MEETS THE EQUIPMENT PRESERVATION AIR REQUIREMENT AND SERVICE AIR REQUIREMENT WE HAVE A ONSHORE AIR COMPRESSORS WHICH IS RUN WHEN THE PLANT IS UNDER SHUTDOWN. THE AIR IS ROUTED THROUGH THE DRIERS IN BARGE TO FULFIL THE REQUIREMENT.

SPECIFICATIONS
TYPE: ROTARY SCREW OIL FREE
MAKE: WATER COOLED SCREW TYPE
MANUFACTURER: INGERSOLL RAND
CAPACITY: 12.7NM3/MIN
PRESSURE: 8.64 BAR G
MOTOR: 120.4 KW/SET
COMPRESSOR PACKAGE DATA
CAPACITY: 18 M3/MIN
RATED OPERATING PRESSURE: 8.5 BAR G
MAX DISCHARGE PRESSURE: 8.7 BAR G
GROSS MASS: 3250 KGS
TOTAL PACKAGE AMPERES: 218/209
VOLTAGE: 380/415 V
PHASE/HERTZ: 3/50
QUANTITY 3 SETS

OFFER 005
E. GAS TURBINE
GAS TURBINES ARE THE MAIN POWER GENERATING UNITS LOCATED ON BARGE TOP DECK. THESE ARE LM6000PC MACHINES, WHICH USES NATURAL GAS AS FUEL FOR CONTINUOUS OPERATION. . THESE ENGINES ARE AERO DERIVATIVE ENGINES MANUFACTURED BY GE. THERE ARE FOUR GT EACH OF 46.68 MW CAPACITY. THESE MACHINES ARE TWIN SHAFT ENGINES. LP SHAFT IS CONNECTED TO GENERATOR AT COLD END THROUGH A REDUCTION GEAR BOX. HP SHAFT IS A FREEWHEELING TYPE SHAFT AND ITS SPEED IS PROPORTIONAL TO LOAD. LP SHAFT HAS LP COMPRESSOR AND LP TURBINE MOUNTED ON IT. HP SHAFT HAS HP COMPRESSOR AND HP TURBINE MOUNTED ON IT.
INLET AIR TO GAS TURBINES ARE FILTERED IN THE FILTER HOUSE WHICH HAS CONICAL FILTERS. INSTRUMENT AIR IS USED TO CLEAN THE FILTERS OF DUST ACCUMULATION. THE AIR IS THEN USED FOR GENERATOR COMPARTMENT PRESSURIZATION, COMBUSTION AND VENTILATION. THE AIR IS COOLED BY CHILLED WATER SUPPLIED FROM CHILLERS PASS THROUGH HEAT EXCHANGER. THE AIR THAN PASSES THROUGH DRIFT ELIMINATOR AND COALESCER BEFORE GOING TO ENGINE AFTER REMOVING THE MOISTURE. THE CONDENSATE GENERATED IN COOLING PROCESS IS USED FORM DM WATER PRODUCTION IN DM PLANT. THE AIR ENERGY IS RAISED THROUGH COMPRESSION AND USED FOR COMBUSTION. AFTER EXPANSION IN TURBINE THE EXHAUST GASES ARE DIVERTED TO OTSG WHERE ITS HEAT ENERGY IS UTILIZED IN GENERATING STEAM. THE TURBINE HAS WATER INJECTION FOR NOX CONTROL.

GAS TURBINE LUBE OIL SYSTEM
A) LUBE OIL FACILITY FOR GAS TURBINE IS INSTALLED ON AUXILIARY PACKAGE.
B) THE SYSTEM CONSISTS OF FOUR MAJOR SECTIONS.
GAS TURBINE LUBE OIL UNIT
ON-ENGINE MOUNTED SUPPLY AND SCAVENGE PUMP
LUBE OIL COOLER UNIT
AIR/OIL SEPARATOR MODULE

GENERATOR AND GEARBOX LUBE OIL SYSTEM
THE LUBE OIL SYSTEM CONSISTS OF TWO MAJOR SECTIONS
SHAFT DRIVEN MAIN LUBE OIL PUMP INTEGRATED ON THE REDUCTION GEARBOX.
LUBE OIL MODULE INCLUDING ELECTRIC MOTOR DRIVEN LUBE OIL PUMP, TWIN WATER-COOLED LUBE OIL COOLERS, FILTERS, AND LUBE OIL TANK.

HYDRAULIC STARTING SYSTEM
THE MAIN COMPONENT OF THE SYSTEM IS AS FOLLOWS:
MOTOR DRIVEN MAIN HYDRAULIC STARTING OIL PUMP WITH HYDRAULIC CONTROL
MOTOR DRIVEN CLUTCH COOLING OIL PUMP
HIGH AND LOW PRESSURE REGULATING VALVES
HYDRAULIC STARTING OIL TANK
SUPPLY AND RETURN FILTERS
HYDRAULIC STARTER
HYDRAULIC STARTING OIL COOLER

AIR INTAKE AND EXHAUST GAS SYSTEM
GAS TURBINE INLET AIR IS DRAWN THROUGH THIS FILTER HOUSE, AND IS LED TO THE GAS TURBINE INLET THROUGH THE AIR SILENCER AND AN INLET SCROLL ASSEMBLY

WATER WASHING SYSTEM
THE MAIN COMPONENTS CONSISTING SYSTEM ARE AS FOLLOWS:
SOLUTION AND RINSE WATER TANK
AC MOTOR DRIVEN PUMP
WATER WASH FILTER
OFF-LINE WATER WASH SPRAY MANIFOLD (ON-ENGINE)
ON-LINE WATER WASH SPRAY MANIFOLD (ON-ENGINE)

FIRE PROTECTION SYSTEM
THE FIRE PROTECTION SYSTEM CONSISTS OF CO2 BOTTLE SKID, RELATED VALVES, PIPE AND INSTRUMENTATION.
THE CO2 IS SUPPLIED TO TWO PLACES AS FOLLOWS,
GAS TURBINE ENCLOSURE
GENERATOR REAR BEARING ENCLOSURE

GENERATOR
A) THE GENERATOR USES OPEN AIR-COOLED, SYNCHRONOUS TYPE, AND TOTALLY ENCLOSED TYPE.
B) THE GENERATOR WILL BE ABLE TO HANDLE ALL LOAD SITUATIONS IN A SATISFACTORY MANNER AT BOTH MAXIMUM AND MINIMUM AMBIENT TEMPERATURE. THE GENERATOR CONSISTS OF THE FOLLOWING COMPONENTS:
(1) ROTOR
(2) STATOR
(3) EXCITER
(4) COOLING SYSTEM
(5) FRAME & ENCLOSURE

GENERAL SPECIFICATION
GT TYPE AERO-DERIVATIVE -LM 6000 PC
MAKE: GE
POWER: 46,688 KW/GT
REVOLUTION: 3600 RPM
COMPRESSOR
TYPE: AXIAL
STAGE: LPC-5 / HPC-14
COMPRESSION RATIO: LPC - 2.4:1 / HPC - 12.5:1
COMBUSTOR
NO OF COMBUSTOR: 1 PER GT
NO OF NOZZLE: 30/COMBUSTOR
COMBUSTOR TYPE: ANNULAR SEQUENTIAL
IGNITION TYPE: ELECTRICAL IGNITER

INLET AIR SYSTEM
MAKE: DONALDSON
FILTER ELEMENTS: STATIC CYLINDRICAL AND CONICAL
NO. OF ELEMENTS: 224 PAIRS (2 * 16 COLUMNS * 7 ROWS)

AIR FLOW: GT COMBUSTION
INITIAL CLEAN SYS: 130 KG/SEC
INITIAL CLEAN FILTER: 93mm W G
PRESSURE DROP: 18.5mm W G

AIR FLOW: GT VENTILATION
INITIAL CLEAN SYS: 25 KG/SEC
INITIAL CLEAN FILTER: 57

AIR FLOW: GENERATOR COOLING AND VENTILATION
INITIAL CLEAN SYS: 1390 CUM/MIN
INITIAL CLEAN FILTER: 42mm W G
PRESSURE DROP: 31.5mm W G

AIR FLOW: GENERATOR BEARING PRESSURISING AIR
INITIAL CLEAN SYS: 30 CU. M/MIN
INITIAL CLEAN FILTER: 50mm W G

FILTER EFFICIENCY:
SODIUM REMOVAL EFFICIENCY: 99.98%
CHLORIDE REMOVAL EFFICIENCY: 99.98%
MOISTURE REMOVAL EFFICIENCY: 99.5% ON 50 MICRO DROPLET

SPRINT SYSTEM
THE TERM “SPRINT” (SPRAY INTERCOOLING) IS A TECHNOLOGICAL ADVANCEMENT THAT HAS BEEN DEVELOPED BY GE INDUSTRIAL AERO DERIVATIVE GAS TURBINES (GE-IAD) TO ENHANCE THE OUTPUT PERFORMANCE OF THE LM6000 GAS TURBINE. THE ADDITION OF GE‟S PROPRIETARY SPRINT TECHNOLOGY INCREASES THE OUTPUT BY 9% AT ISO AND BY MORE THAN 20% ON 90° F (32°C) DAYS. THE EFFECTIVENESS OF THE SYSTEM BECOMES MORE PRONOUNCED AS AMBIENT TEMPERATURES RISE.
THE SPRINT SYSTEM BEGINS A MIST INJECTION PROCESS ONCE THE TURBINE REACHES FULL LOAD OPERATION; NO ENHANCEMENT BENEFITS ARE ACHIEVED AT PART LOAD FOR EITHER POWER AUGMENTATION OR DECREASED HEAT RATE.
THE SPRINT COOLING TECHNOLOGY LOWERS THE HIGH-PRESSURE COMPRESSOR (HPC) INLET TEMPERATURE (T2.5), WHICH IN TURN EFFECTIVELY LOWERS THE HPC COMPRESSOR DISCHARGE TEMPERATURE (T3).

ISO-INTERNATIONAL STANDARDS ORGANIZATION
AMBIENT TEMPERATURE 59 F (15 C)
BAROMETRIC PRESSURE 14.6% (101.4 KPA)
RELATIVE HUMIDITY 60%
ELEVATION SEA LEVEL
INLET AND EXHAUST LOSSES-NONE
EMISSION CONTROLS-NONE

THE SYSTEM CONSISTS OF TWO MULTI-NOZZLE INTER STAGE MIST INJECTION SYSTEMS
1) THE LOW-PRESSURE COMPRESSOR (LPC) MIST INJECTION SYSTEM CONSISTS OF A SINGLE ROW OF 23 NOZZLES LOCATED IN THE INLET OF THE LPC.
2) THE HIGH-PRESSURE COMPRESSOR (HPC) MANIFOLD IS SPLIT INTO TWO (2) SEPARATE MANIFOLDS (INNER / OUTER) CONSISTING OF TWO ROWS OF 12 NOZZLES EACH FOR A COMBINED TOTAL OF 24 NOZZLES. THE HPC MANIFOLDS ARE LOCATED IN THE COMPRESSOR FRONT FRAME SUPPORT HOUSING BETWEEN THE LPC AND HPC.

ONLY ONE MANIFOLD WILL BE OPERATIONAL AT A GIVEN TIME. WHICH MANIFOLD IS ENERGIZED IS DEPENDENT ON THE INLET AIR TEMPERATURE. INLET AIR TEMPERATURES OF ≥ 48°F ENABLES THE LPC SOV VALVE TO BE OPENED WHEN THE SYSTEM IS ENABLED. WHEN TEMPERATURE DROP BELOW 48°F THE LPC MANIFOLD WILL BE DE-ENERGIZED AND HPC MANIFOLD ENERGIZED. IF THE TEMPERATURE CONTINUES TO DROP, AT 41°F BOTH HPC AND LPC WILL BE DE- ENERGIZED. AS TEMPERATURES INCREASE FROM BELOW 41°F THE HPC MANIFOLD WILL BE REENERGIZED AT 43°F INCREASING AND AT 50°F INCREASING THE LPC MANIFOLD WILL BE REENERGIZED AND HPC MANIFOLD DE-ENERGIZED.

AIR EXTRACTED FROM THE ENGINE 8TH STAGE HPC BLEED AIR EXTRACTION PORT IS UTILIZED TO ATOMIZE & PRESSURIZE THE SYSTEM BY USING THE SPRINT SPRAY INTER-COOLING SYSTEM, THE COMPRESSOR PRESSURE RATIO CAN BE INCREASED AND ADDITIONAL AIR CAN BE DIRECTED THROUGH THE COMPRESSOR TO INCREASE THE GAS TURBINE CHARACTERISTICS

SPECIFICATIONS
PUMP TYPE: VERTICAL MULTI STAGE CENTRIFUGAL PUMP
MATERIAL: STAINLESS STEEL
CATALOGUE NO: 3SVDK15SCP
PRESSURE: P SI 360 MAX
TEMPERATURE: 250 F MAX
MANUFACTURER: GOULDS PUMPS, ITT, G&L SERVICES SSV
FLOW RANGE: 1 1 TO 75 GPM
PUMP EFFICIENCY: 65%
MOTOR POWER: 3/4 HP

FILTER
TYPE: DUPLEX
MANUFACTURER: INDUFIL BV, NETHERLAND
YEAR: 2007

SKID MOUNTED EQUIPMENT
DEMINERALISED WATER IS SUPPLIED TO THE SPRINT SYSTEM FROM DM PLANT. IT IS SUPPLIED AT A RATE OF 10-GPM MINIMUM TO 30 GPM MAXIMUM AND AT PRESSURES 0-65 PSIG. AFTER INTERFACE CONNECTION, IT FLOWS THROUGH A Y-TYPE STRAINER, A NORMALLY OPEN BALL VALVE TO A CENTRIFUGAL PUMP. THE CENTRIFUGAL PUMP IS DRIVEN BY MOTOR RATED AT 10 HP. AFTER THE PUMP, THE DEMINERALISED WATER PRESSURE IS MONITORED BY PRESSURE SWITCH LOW PSL-62227 WHICH ACTIVATES PRESSURE ALARM LOW PAL- 62227 IN THE EVENT THE WATER PRESSURE FALLS BELOW 75 PSIG. PRESSURE GAUGE PI-62229 SCALED 0-400 PSIG DISPLAYS PUMP DISCHARGE PRESSURE. THE DEMINERALISED WATER THEN FLOWS THROUGH A FLOW METER, SOLENOID ACTUATED BLOCK VALVE, AND ENTERS A DUPLEX FILTER THAT FILTERS THE WATER TO 20 MICRONS ABSOLUTE. PRESSURE DIFFERENTIAL SWITCH HIGH PDSH-62233 MONITORS THE DIFFERENTIAL PRESSURE ACROSS THE FILTERS AND ACTIVATES AN ALARM SHOULD THE DIFFERENTIAL PRESSURE INCREASE TO 10 PSID. PRESSURE DIFFERENTIAL INDICATOR PDI-62232 PROVIDES A VISUAL DISPLAY OF THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.
LPC SPRINT – 17 GPM (64 L/MIN)
HPC SPRINT – 13 GPM (50 L/MIN), 6.5 GPM (25 L/MIN) PER MANIFOLD

SYSTEM PRESSURIZATION AIR
AIR FOR ATOMIZING AND PRESSURIZING THE SPRINT SYSTEM IS EXTRACTED FROM THE 8TH STAGE HPC AT ENGINE. THE AIR IS SUPPLIED AT 630 SCFM (18 SCMM) AND 150 PSIA (1034 KPAG) THROUGH AN ORIFICE. THE AIR FLOW IS DIVIDED INTO TWO SEPARATE FLOW ONE FOR LP SPRINT AND THE OTHER FOR HP SPRINT.
SYSTEM PURGE AIR IS USED TO PURGE DEMINERALIZED WATER FROM THE SYSTEM FOR APPROXIMATELY TWO MINUTES IMMEDIATELY AFTER SPRINT SHUTDOWN. THIS IS CONDUCTED TO PREVENT CORROSION AND THE POSSIBILITY OF ICE FORMATION. SYSTEM PURGE AIR IS PROVIDED FROM THE CUSTOMER‟S CONNECTION AT 80-120 PSIG, DRY FILTERED TO 5 MICRONS ABSOLUTE.

FUEL INJECTION SYSTEM
TYPE: GAS FUEL SYSTEM WITH NOX INJECTION
THE LM6000 PC FUEL SYSTEM INCLUDES FUEL MANIFOLDS, FLEXIBLE FUEL HOSES, AND 30 FUEL NOZZLES. THE MINIMUM TEMPERATURE OF THE GAS FUEL SUPPLIED TO THE GAS TURBINE SHALL BE 50°F (27.8°C) GREATER THAN THE SATURATED VAPOUR TEMPERATURE OF THE GAS SUPPLY PRESSURE. THE TEMPERATURE OF THE GAS FUEL SHOULD NOT EXCEED 300°F (148.8°C) AT THE GAS MANIFOLD INLET

OFFER 006
F. STEAM TURBINE
STEAM TURBINE EXPANDS THE STEAM GENERATED FROM ALL THE OTSG TO GENERATE POWER. HP AND LP STEAM GENERATED FROM ALL 4 OTSG BY UTILIZING THE HEAT IN EXHAUST FLUE GASES, IS DIRECTED TO COMMON HEADER. STEAM FROM HP AND LP HEADERS ARE INJECTED IN THE STEAM TURBINE THROUGH CONTROL VALVES. LP STEAM IS INJECTED AT 29TH STAGE OF THE TURBINE. THE STEAM GETS EXPANDED OVER THE REACTION BLADES AND AFTER UTILIZATION OF WORK IS DUMPED INTO THE AXIAL FLOW DEAERATOR CUM CONDENSER. THE STEAM GETS CONDENSED IN THE CONDENSER AND FEED WATER FROM CONDENSER HOT WELL IS DIRECTED BACK TO THE OTSG THROUGH BOILER FEED PUMPS. CONDENSATE POLISHING UNIT PURIFIES THE FEED WATER BEFORE IT ENTERS THE OTSG. STEAM JET AIR EJECTOR AND VACUUM PUMP ARE USED TO GENERATE AND MAINTAIN VACUUM IN THE CONDENSER. THE TWO-POLE GENERATOR USES AIR COOLING FOR THE ROTOR WINDING AND THE STATOR WINDING. THE LOSSES IN THE REMAINING GENERATOR COMPONENTS, SUCH AS IRON LOSSES, WINDAGE LOSSES, AND STRAY LOSSES, ARE ALSO DISSIPATED THROUGH AIR.
THE AC EXCITER IS PROVIDED TO SUPPLY THE FIELD CURRENT TO THE ROTOR WINDING OF THE GENERATOR.
THE BRUSHLESS EXCITER SYSTEM IS CONSISTS OF THREE PHASE MAIN EXCITER (AC EXCITER), ROTARY RECTIFIER (R-RF), PILOT EXCITER (PERMANENT MAGNETIC GENERATOR) AND AVR (AUTOMATIC VOLTAGE REGULATOR).THE TURBINE IS AN AXIALFLOW, SINGLE CASING CONSTRUCTION WITH APPROX. 50% OF REACTION.

TURBINE BYPASS SYSTEM
THERE ARE FOUR BYPASS STATIONS IN THE TANIR BAVI (GEL, KAKINADA) POWER PLANT. TWO OF THEM ARE HP BYPASS STATIONS AND OTHER TWO LP BYPASS STATIONS.
EACH HP AND LP BYPASS STATIONS ARE CONNECTED TO HP AND LP STEAM LINE OF TWO OTSG (ONCE-THROUGH STEAM GENERATOR). THE BYPASS STATIONS FUNCTIONS ARE DESCRIBED BELOW.
EACH BYPASS STATIONS CONSISTING OF:
ONE STEAM SHUT OFF VALVE PER BYPASS
ONE STEAM PRESSURE CONTROL VALVE PER BYPASS
ONE WATER INJECTION CONTROL VALVE PER BYPASS
ONE STEAM ASSISTING/PREHEATING PER BYPASS

HP STEAM BY-PASS VALVE
INLET STEAM PRESSURE: 60.0 BAR A
INLET STEAM TEMPERATURE: 419 °C
INLET STEAM FLOW: 82.6 T /H
OUTLET STEAM PRESSURE: 5.0 BAR A
OUTLET STEAM TEMPERATURE APP: 162 °C
COOLING WATER: FEED WATER

LP STEAM BY-PASS VALVE
INLET STEAM PRESSURE: 5.8 BARA
INLET STEAM TEMPERATURE: 240 °C
INLET STEAM FLOW: 30.6 T /H
OUTLET STEAM PRESSURE: 3.0 BAR A
OUTLET STEAM TEMPERATURE APP: 143 °C
COOLING WATER: FEED WATER

STEAM TURBINE GENERATOR
TYPE: K9V
MANUFACTURER: ABB GENERATION
TYPE: GTL 1200 GC
NUMBER OF POLES (PAIR): 2(1)
PROTECTION CLASS: 54
CHARACTERISTIC GENERATOR CURVE NO: TT/1, TT/4
RATED APPARENT POWER AT DESIGN CONDITIONS: 64.7 MVA
RATED POWER FACTOR (LAGGING): 0.85 COS PHI
RATED VOLTAGE: 11 KV
VOLTAGE VARIATION RANGE AT FULL LOAD: +5 TO -5 %
RATED CURRENT: 3396 A
RATED FREQUENCY: 50 HZ
RATED SPEED: 3000 RPM
EFFICIENCY AT 100% BASE LOAD AND POWER FACTOR 0.8: 98.48 %
STATOR WINDING - COOLING MEDIUM: AIR
MAX. OUTLET TEMPERATURE OF COOLING MEDIUM: 80 °C
ROTOR WINDING - COOLING MEDIUM: AIR
MAX. OUTLET TEMPERATURE OF COOLING MEDIUM: 85 °C
PRESSURE OF COOLING MEDIUM: BAR (G)
SYNCHRONOUS REACTANCE SATURATED, XQ: %

OFFER 007
G. FEEDWATER SYSTEM
THE FUNCTION OF THE FEEDWATER SYSTEM IS TO PROVIDE BOILER FEEDWATER TO THE FOLLOWINGS:
FEEDING OF THE HP AND LP FEEDWATER
FEEDING FEEDWATER TO THE ATTEMPERATOR SPRAYS FOR THE HP AND LP BY-PASS SYSTEM.
THE FEEDWATER SYSTEM DESIGN FLOW IS BASED ON THE HEAT BALANCE FOR THE MCR CONDITION INCLUDING SPRAY WATER FOR STEAM TURBINE BY-PASS OPERATION.
THE HP/LP FEEDWATER PUMPS ARE SIZED WITH 10% MARGIN ON HEAD LOSS

BOILER FEED PUMP
TYPE: HORIZONTAL CENTRIFUGAL PUMP
NUMBER OF PUMPS: 6
MODEL NO: 80*65SS 14M
CAPACITY (HP/LP): HP 54 M3/HR. LP 17 M3/HR
SPEED: 2980 RPM
DESIGN TEMPERATURE: 41°C
FLUID HANDLED: FEED WATER
TDH (HP/LP): 957 M/ 267 M
POWER (BHP): 206.85 KW
HTP: 152.48 BAR G
WEIGHT: 5190 KG
MAKE: HYOSUNG-EBARA CO LTD
OIL: AWT-32

MOTOR
TYPE: 3D SQUIRREL CAGE INDUCTION MOTOR
FRAME: 400
POWER: 240 KW
POLES: 2
VOLTAGE: 6600 V
CURRENT: 24.9 A
FREQUENCY: 50 HZ
CODE LETTER: F
RATING: S1
EFFICIENCY: 93.5%
COS D: 0.900
INSULATION CLASS: F
AMB TEMPERATURE: 50°C
TEMP RISE: 70°C
SPACE HEATER: 1D, 240 V, 238 W
BEARING (DE/NDE): NU217MC4+6217C4
TOTAL WEIGHT: 2800 KG
MANUFACTURING DATE: 2000, 06
MAKE: HYUNDAI

AMMONIA/ HYDRAZINE DOSING
AMMONIA SOLUTION TANK
TYPE: VERTICAL CYLINDRICAL
CAPACITY: 300 L

HYDRAZINE SOLUTION TANK
TYPE: VERTICAL CYLINDRICAL
CAPACITY: 300 L

AMMONIA DOSING PUMP
TYPE: METERING PUMP
CAPACITY: 5.0 L/HR @ 20.7 BAR G
MAKE: LIQUID DYNAMICS
M.A.W.P: 3000 BAR AT 100°C
MIN.D. METAL TEMP: 20 F
SEAL MATERIAL: E.MAX 170 F MIM -50 F
MEMBRANE MATERIAL: E.MAX 170 F MIM -50 F
RECOMMENDED REFILL PRESSURE: 2400 PSI

AGITATOR
MODEL: 8641-99
POWER: 0.25 HP
VOLTAGE: 240 V
FLA: 2.4
INS CLASS: F
ENC: TEFC
FRAME: 56C
DUTY: CONTINUOUS
SPEED: 960 RPM
FREQUENCY: 50 HZ
SF: 1.0
MAX AMBIENT: 50°C
BEARING: 6023

OFFER 008
H. CLOSED COOLING WATER SYSTEM
THE FUNCTION OF THE CIRCULATING WATER SYSTEM IS TO PROVIDE COOLING WATER TO THE MAIN CONDENSER TO CONDENSE TURBINE EXHAUST STEAM FOR REUSE IN THE TURBINE CYCLE AND TO THE CLOSED COOLING WATER COOLERS INCLUDING G/T INLET AIR CHILLERS TO REMOVE HEAT LOADS FROM VARIOUS PLANT COMPONENTS.

TECHNICAL DATA
A) AUX. C.W BOOSTER PUMP
MOTOR
MODEL: HK165SR259FB
FRAME: 160L
DUTY: CONT
TYPE: HK-50
BEARINGS (DRIVE/OPPOSITE): 6309ZZC3/6309ZZC3
ENCLOSURE: IP54
CODE: G
INSULATION CLASS: F
S.F: 1.0
NEMA DESIGN: B
POWER (KW/HP): 15/20
POLES: 4
VOLTAGE: 415 V
CURRENT: 28.8A
FREQUENCY: 50 HZ
NEMA NOMINAL EFFICIENCY: 88.5%
SPEED: 1465 RPM
MAX AMBIENT: 50°C
REF NO: 0F114083-002
WEIGHT: 143 KG

PUMP
TYPE: HORIZONTAL CENTRIFUGAL PUMP
MODEL: NO HES 150 TO 200
CAPACITY: 260 M3/HR
TDH: 10 M
SPEED: 1450 RPM
POWER: 9.6 KW
DESIGN TEMPERATURE: 29°C
HTP: 11.8 BAR
FLUID HANDLED: SEA WATER
TOTAL WEIGHT: 323 KG
BEARING: 6307
MAKE: HYOSUNG-EBARA CO LTD

OFFER 009
I. AUXILIARY COOLING WATER SYSTEM
THE FUNCTION OF THE CLOSED COOLING WATER SYSTEM IS TO REMOVE THE WASTE HEAT FROM THE COMPONENTS OF VARIOUS PLANT EQUIPMENT AND REJECTS IT THROUGH THE CCW COOLERS.

DESIGN BASIS
THE SYSTEM IS DESIGNED TO REMOVE HEAT FROM THE COMPONENTS IN A SAFE, RELIABLE, AND ECONOMICAL MANNER WITH MINIMAL VIBRATION AND NOISE. THERE ARE SEPARATED TWO (2) CLOSED COOLING WATER SYSTEMS FOR SIMPLE CYCLE OPERATION AND COMBINED CYCLE OPERATION.
THE CLOSED COOLING WATER SYSTEM CONTINUOUSLY SUPPLIES DEMINERALIZED (PASSIVATED) QUALITY WATER AS A COOLING MEDIUM FOR THE PLANT EQUIPMENT IN THE CLOSED LOOP COOLING SYSTEM.

COOLING WATER IS SUPPLIED TO THE FOLLOWING EQUIPMENT.
SIMPLE CYCLE COOLING GT
GENERATOR COOLER GT LUBE
OIL COOLERS HYDRAULIC
STARTING OIL COOLERS
AIR COMPRESSOR COOLERS

COMBINED CYCLE COOLING
SAMPLING COOLER
ST GENERATOR AIR COOLER
ST LUBE OIL COOLERS
WATER BOX PRIMING PUMP COOLERS

TECHNICAL DATA
SIMPLE CYCLE CLOSED COOLING WATER PUMP
TYPE: HORIZONTAL, CENTRIFUGAL
QUANTITY: TWO (2) SET
CAPACITY: 510 M3/HR
SPEED: 1485 RPM
DESIGN TEMPERATURE: 40°C
FLUID HANDLED: DEMINERALIZED WATER
MODEL NO: HES 200-330

OFFER 010
J. CONDENSATE POLISHING UNIT (CPU)
THE CONDENSATE POLISHING SYSTEM TREATS OTSG FEED WATER AND PROVIDES FEED WATER QUALITY SUITABLE FOR IT‟S USE.
THE CPU PACKAGE CONSISTS TO 2 X 100% CONDENSATE POLISHING VESSELS 1X100%, BACK WASHING PUMP, AND POWDEX COATING SYSTEM.

CONDENSATE POLISHING SYSTEM
CONDENSATE POLISHER INLET QUALITY
SUSPENDED SOLIDS, PPB
NORMAL QUALITY: 1000
STARTUP OR INLEAKAGE: 2500 TO 5000

TDS (LESS NH3), PPB
NORMAL QUALITY: 1000
STARTUP OR INLEAKAGE: 2000

REACTIVE SiO2, AS SiO2, PPB
NORMAL QUALITY: <100
STARTUP OR INLEAKAGE: 100 TO 500

TOTAL Fe, AS Fe, PPB
NORMAL QUALITY: <100
STARTUP OR INLEAKAGE: 100 TO 500

TOTAL Ca, AS Ca, PPB
NORMAL QUALITY: <50
STARTUP OR INLEAKAGE: 50 TO 100

Na, AS Na, PPB
NORMAL QUALITY: 25
STARTUP OR INLEAKAGE: 50

CATION CONDUCTIVITY, S/CM
NORMAL QUALITY: 3
STARTUP OR INLEAKAGE: 3 TO 5

PH
NORMAL QUALITY: 8 TO 9.4
STARTUP OR INLEAKAGE: 8 TO 10

2) CONDENSATE POLISHER OUTLET QUALITY
SUSPENDED SOLIDS, PPB
STARTUP OR INLEAKAGE: 5
NORMAL QUALITY: 90% REMOVAL (2)

TDS (LESS NH3), PPB
STARTUP OR INLEAKAGE: 25
NORMAL QUALITY: 90% REMOVAL UP TO PH 9.6

REACTIVE SiO2, AS SiO2, PPB
STARTUP OR INLEAKAGE: 10 (4)
NORMAL QUALITY: 90% REMOVAL UP TO PH 9.6 OR 20PPB WHICHEVER IS GREATER

TOTAL Fe, AS Fe, PPB
STARTUP OR INLEAKAGE: 5
NORMAL QUALITY: 90 % REMOVAL

TOTAL Ca, AS Ca, PPB
STARTUP OR INLEAKAGE: 2
NORMAL QUALITY: 90% REMOVAL UP TO PH 9.6

Na, AS Na, PPB 5 (4)
STARTUP OR INLEAKAGE: 90%
NORMAL QUALITY: REMOVAL UP TO PH 9.6 OR 10 PPB WHICHEVER IS GREATER

CATION CONDUCTIVITY, S/CM
STARTUP OR INLEAKAGE: 0.1
NORMAL QUALITY: 0.2

OFFER 011
K. WASTE WATER SYSTEM
THE FUNCTION OF WASTE WATER SYSTEM IS TO COLLECT OILY WASTEWATER AND CHEMICAL WASTEWATER, INTO THE WASTE WATER DRAIN TANK SEPARATELY.
THE COLLECTED WASTEWATER WILL BE DELIVERED TO THE OIL SEPARATOR OR WASTEWATER TREATMENT SYSTEM ON-SHORE, WHICH IS SUPPLIED BY OTHERS BEFORE EFFLUENT TO DISCHARGE.
STG OR GTG LUBE OIL WILL BE DRAINED TO THE LUBE OIL DRAIN TANK FOR INSPECTION OR MAINTENANCE.

DESIGN BASIS
WASTE WATER CHARACTERISTICS:
DESCRIPTION: OILY WASTEWATER
CHARACTERISTIC: OILY WATER
SOURCE: EQUIPMENT DRAINAGE
COLLECT TANK CAPACITY: 120M3
DISPOSAL: OIL SEPARATOR

DESCRIPTION: T/R DRAIN WASTEWATER
CHARACTERISTIC: OIL OR OILY WATER
SOURCE: TRANSFORMER EQUIPMENT
COLLECT TANK CAPACITY:
DISPOSAL: OIL SEPARATOR

DESCRIPTION: CHEMICAL WASTEWATER
CHARACTERISTIC: CHEMICAL
SOURCE: EQUIPMENT CHEMICAL CLEANING
COLLECT TANK CAPACITY: 50M3
DISPOSAL: W/T PLANT

DESCRIPTION: LUBE OIL DRAIN WASTE WATER
CHARACTERISTIC: LUBE OIL
SOURCE: LUBE OIL TANK
COLLECT TANK CAPACITY: 12M3
DISPOSAL: LUBE OIL TANK OR DISPOSAL TO ON-SHORE

THE OILY WASTE WATER SYSTEM INCLUDED THE FOLLOWING PUMPS OILY WASTE WATER PUMPS:
OILY WASTEWATER PUMP: 60M3/HR X 45MH X 2 SETS
TAG NO: ED-M-PP02-B
CAPACITY: 60 CU.M/HR
SPEED: 1480 RPM
DESIGN TEMPERATURE: 32°C
FLUID HANDLED: SEA WATER
TYPE: HORIZONTAL CENTRIFUGAL
MODEL NO: GMC 100D
TDH: 3 2 M
POWER: 8 KW
HYDRO TEST PRESSURE: 3.8 BAR G
TOTAL WEIGHT: 272 KG
BEARINGS: 6308/6308
MANUFACTURER: HYOSUNG EBARA CORPORATION
YEAR OF MANUFACTURE: SEP 2000

OFFER 012
L. PLANT ELECTRICAL SYSTEM
THE PLANT GENERATES POWER AT 11KV AND EVACUATES POWER TO 220KV SWITCHYARD FROM EACH OF GENERATOR STEP-UP TRANSFORMER ON BARGE THROUGH OVER-HEADLINES. THERE ARE THREE STEP UP TRANSFORMERS
1. GST#1- 11KV/11KV/220KV-120MVA THREE WINDING TRANSFORMER
2. GST#2-11KV/11KV/220KV -120 MVA THREE WINDING TRANSFORMER
3. SST -11KV/220KV -70MVA TWO WINDING TRANSFORMER
GST IS THREE WINDING TRANSFORMER WITH INPUT FROM TWO GAS TURBINE GENERATOR AT LV SIDE (11KV) AND OUTPUT AT HV SIDE (220KV). SST IS TWO WINDING TRANSFORMER WITH INPUT FROM STEAM TURBINE GENERATOR AT 11KV SIDE AND OUTPUT OF 220KV AT HV SIDE.
ALSO THE 11KV IS STEPPED DOWN TO 6.6KV THROUGH UNIT AUXILIARY TRANSFORMERS UAT#1 AND UAT#2 FOR THE PLANT AUXILIARY POWER. 6.6KV IS USED FOR RUNNING THE BOILER FEEDER PUMPS AND CHILLERS DURING PLANT OPERATION AND ALSO STEPPED DOWN TO 415V THROUGH AUXILIARY TRANSFORMERS AT#1, AT#2, AT#3 AND AT #4 FOR THE PLANT AUXILIARY.

DESIGN CRITERIA
THE SYSTEM PARAMETERS FOR UTILITY ARE DETAILED BELOW
SYSTEM: 220KV, 50HZ, 3PH, 3WIRE
FAULT LEVEL: 31.5KA/1SEC
SYSTEM EARTHLING: SOLID EARTHLING (BIL; 950KV)

SYSTEM: 11.0KV, 50HZ, 3PH, 3WIRE
FAULT LEVEL: 50KA/3SEC
SYSTEM EARTHLING: NEUTRAL EARTHED THROUGH NGTR (<10A)

SYSTEM: 6.6KV, 50HZ, 3PH, 3WIRE
FAULT LEVEL: 20KA/1SEC
SYSTEM EARTHLING: LOW RESISTANCE THROUGH NGR (1200A)

SYSTEM: 415V, 50HZ, 3PH, 4WIRE
FAULT LEVEL: 50KA/1SEC
SYSTEM EARTHLING: SOLID EARTHLING

THE SYSTEM/EQUIPMENT ARE DESIGNED AS PER THE FOLLOWING:
MOTORS/SYSTEM: MOTORS ABOVE200KW
VOLTAGE: 6.6KV
SYSTEM EARTHING: LOW RESISTANCE

MOTORS/SYSTEM: MOTORS 1KWUP TO 200KW
VOLTAGE: 415V
SYSTEM EARTHING: SOLID

MOTORS/SYSTEM: MOTORS BELOW1KW
VOLTAGE: 240V
SYSTEM EARTHING: SOLID

MOTORS/SYSTEM: CONTROLS FOR MCC UPS
VOLTAGE: 110VAC
SYSTEM EARTHING: SOLID

MOTORS/SYSTEM: SUPPLY ILLUMINATION
VOLTAGE: 110VAC
SYSTEM EARTHING: EARTHED

MOTORS/SYSTEM: SYSTEM
VOLTAGE: 240VAC
SYSTEM EARTHING: SOLID

MOTORS/SYSTEM: SPACE HEATER FOR PANEL/MOTOR 55KW& ABOVE
VOLTAGE: 240VAC
SYSTEM EARTHING: SOLID

MOTORS/SYSTEM: DC SYSTEM
VOLTAGE: 110VDC
SYSTEM EARTHING: UNEARTHED

M.V SWITCHGEAR
M.V SWITCHGEAR IS COMPOSED OF VACUUM CIRCUIT BREAKER (VCB) FOR 6.6KV MOTORS AND POWER FEEDING TO 415V COMMON

MCC AND ON-SHORE, CONTROL/METERING INSTRUMENTS, INTEGRATED DIGITAL RELAYS FOR PROTECTION, ETC.
L.V SWITCHGEAR IS COMPOSED OF FOUR (4) COMMON MCC, EACH OF THEM HAVING INCOMING AIR CIRCUIT BREAKER (ACB), MCCB FOR OUTGOING FEEDERS, CONTROL/METERING INSTRUMENTS, ETC.

DC / UPS SYSTEM
BATTERY BACKED D.C SYSTEM CONSISTED OF REDUNDANT BATTERY CHARGERS AND TWO BATTERY BANKS ARE PROVIDED.
FOR CRITICAL LOADS REDUNDANT FEEDERS WITH AUTO-CHANGEOVER SCHEME IS PROVIDED.
SOME OF THE LOADS ALSO REQUIRE A SECURE A.C SUPPLY FOR ITS OPERATION. FOR THESE LOADS, STATION DC FED INVERTER SYSTEM, GENERALLY KNOWN AS UNINTERRUPTED POWER SUPPLY (UPS) IS PROVIDED FOR THE FOLLOWINGS:
DCS
COMMUNICATION SYSTEM
CONTROL, PROTECTION SYSTEM ETC.

LIGHTING SYSTEM
LIGHTING SYSTEM IS DESIGNED TO PROVIDE APPROPRIATE ILLUMINATION FOR THE PLANT IN ALL TIMES CONSIDERING THE NATURE OF WORK TO BE CARRIED OUT.
THE POWER SUPPLY FOR LIGHTING SYSTEMS SHALL BE DERIVED FROM THE FOLLOWING SOURCES.
NORMAL A.C SYSTEM
EMERGENCY LIGHTING SYSTEM (DC)
BATTERY BACKED EXIT LIGHTING

FLUORESCENT LAMPS ARE USED FOR OFFICES, SWITCHGEAR ROOM, ETC. HIGH-PRESSURE SODIUM VAPOR LAMPS & METAL HALIDE AND LED LAMPS SHALL BE USED FOR HIGH BAY INDOOR AREA AND OUTDOOR AREA RESPECTIVELY AS APPROPRIATE.

GROUNDING & LIGHTNING PROTECTION
THE GROUNDING & LIGHTNING SYSTEM IN GENERAL COVER THE FOLLOWINGS:
SYSTEM NEUTRAL GROUNDING
EQUIPMENT GROUNDING FOR PERSONNEL SAFETY
LIGHTNING PROTECTION

ALL METALLIC, NON-CURRENT CARRYING PARTS OF ALL APPARATUS SUCH AS TRANSFORMERS, SWITCHGEAR PANELS, CONTROL & PROTECTION PANELS, CABLE TRAYS, CRANE RAILS, STEEL STRUCTURES, ETC. ARE BOUNDED WITH GROUNDING SYSTEM.

POWER SUPPLY TO ON-SHORE
FOR ON-SHORE PLANT, THE FOLLOWINGS ARE PROVIDED FROM THE BARGE;
6.6KV REDUNDANT FEEDERS THROUGH INTERCONNECTING CABLE SUPPORT
415V EMERGENCY POWER IN REDUNDANT FEEDERS THROUGH INTERCONNECTING CABLE SUPPORT

POWER TRANSFORMERS GST 1 & GST 2
RATING: 3 PHASE / 120 MVA
VOLTAGE: 220/11/11 KV
CAPACITY HV/LV1/LV2: 120/60/60
COOLING: ONAN/ONAF
BIL (KVP): 1050/75/75
FREQUENCY: 50 HZ
CONNECTION & SYMBOL: STAR/DELTA/DELTA – YND11D11
NEUTRAL GROUNDING: HV SOLIDLY GROUNDED
TYPE OF CONSERVATOR: AIR CELL TYPE (COPS)
TYPE OF TANK: CONVENTIONAL TYPE WITH BOLTED COVER
TYPE OF TAP CHANGER: OFF CIRCUIT TAPPING SWITCH
COOLING EQUIPMENTS: RADIATOR WITH FANS
TYPE OF BUSHING: HV – 245 KV OIP CONDENSER BUSHING
LV 1 & LV 2 – 17.5 KV PORCELAIN BUSHING
HV NEUTRAL – 36 KV PORCELAIN BUSHING
NO LOAD LOSS: 90 KW
NO LOAD CURRENT: 1 %
NOISE LEVEL: 85 DB
LOAD LOSSES: 340 KW
TEMPERATURE RISE: OIL – 35 DEG.C & WINDING – 45 DEG.C
VOLTAGE VARIATION: + 5 TO – 5 % OF HV – SWITCH

POWER TRANSFORMER SST
RATING: 3 PHASE / 70 MVA
VOLTAGE: 220/11 KV
CAPACITY HV/LV: 70
COOLING: ONAN/ONAF
BIL (KVP): 1050/75
FREQUENCY: 50 HZ
CONNECTION & SYMBOL: STAR/DELTA – YND11
NEUTRAL GROUNDING: HV SOLIDLY GROUNDED
TYPE OF CONSERVATOR: AIR CELL TYPE (COPS)
TYPE OF TANK: CONVENTIONAL TYPE WITH BOLTED COVER
TYPE OF TAP CHANGER: OFF CIRCUIT TAPPING SWITCH
COOLING EQUIPMENTS: RADIATOR WITH FANS
TYPE OF BUSHING: HV – 245 KV OIP CONDENSER BUSHING
LV – 17.5 KV PORCELAIN BUSHING
HV NEUTRAL – 36 KV PORCELAIN BUSHING
NO LOAD LOSS: 46 KW
NO LOAD CURRENT: 1 %
NOISE LEVEL: 85 DB
LOAD LOSSES: 260 KW
TEMPERATURE RISE: OIL – 35 DEG.C & WINDING – 45 DEG.C
VOLTAGE VARIATION: + 5 TO – 5 % OF HV – SWITCH

UNIT AUXILIARY TRANSFORMERS UAT 1 & UAT 2
RATING: 3 PHASE / 18.5 MVA
VOLTAGE: 11/6.9 KV
CAPACITY HV/LV: 18.5
COOLING: ONAN/ONAF
BIL (KVP): 75/7 5
FREQUENCY: 50 HZ
CONNECTION & SYMBOL: DELTA/STAR – DYN1
NEUTRAL GROUNDING: LV THROUGH NEUTRAL GROUNDING RESISTOR
TYPE OF CONSERVATOR: COPS
TYPE OF TANK: CONVENTIONAL TYPE WITH BOLTED COVER
TYPE OF TAP CHANGER: ON LOAD TAP CHANGER, MAKE – EASUN-MR 2 X V III
350 D 10.19.1N W, 19 POSITION WITH MA
2 MOTOR DRIVEN MECHANISM
COOLING EQUIPMENTS: RADIATOR WITH FANS
TYPE OF BUSHING: HV – 17.5 KV PORCELAIN BUSHING
LV – 17.5 KV PORCELAIN BUSHING
LV NEUTRAL – 17.5 KV PORCELAIN BUSHING
NO LOAD LOSS: 15 KW
NO LOAD CURRENT: 1 %
NOISE LEVEL: 85 DB
LOAD LOSSES: 130 KW
TEMPERATURE RISE: OIL – 55 DEG.C & WINDING – 60 DEG.C
VOLTAGE VARIATION: + 10 TO – 12.5 % OF HV – OLTC

AUXILIARY TRANSFORMERS AT 1, AT 2, AT 3 & AT 4
TYPE: 3 PHASE / CAST RESIN MOULDED TRANSFORMER
RATING: 2.5 MVA
VOLTAGE HV/LV: 6.6/0.413 KV
FREQUENCY: 50 HZ
TYPE OF TAP CHANGER: NO VOLTAGE TAP LINK (+/- 2.5 % X 2)
TAP VOLTAGE: F 6.93 / 6.765, R 6.6 / 6.434 / 6.27 KV
WINDING CONNECTION: DYN11
COOLING METHOD: AN
% IMPEDANCE: 10.7 (IEC TOLERANCE)
TEMPERATURE RISE: PRIMARY WINDING – 70 DEG.C
SECONDARY WINDING – 90 DEG.C
WINDING INSULATION CLASS: PRIMARY VOLTAGE – BIL 60 KV
NOISE LEVEL: 70 DB
NO LOAD LOSSES: 5.6 KW
LOAD LOSSES: 19 KW

LIST OF ONSHORE AND OFFSHORE AC EQUIPMENTS:
MAKE: CARRIER
TYPE: PACKAGE
LOCATION: BARGE CONTROL ROOM
EACH CAPACITY: 8
TOTAL CAPACITY IN TR: 8
QUANTITY: 1

MAKE: CARRIER, BLUE STAR
TYPE: PACKAGE
LOCATION: RACK ROOM
EACH CAPACITY: 8, 11
TOTAL CAPACITY IN TR: 19
QUANTITY: 2

MAKE: CARRIER
TYPE: PACKAGE
LOCATION: ROOF TOP
EACH CAPACITY: 20
TOTAL CAPACITY IN TR: 20
QUANTITY: 1

MAKE: BLUE STAR
TYPE: DUCTING SPLIT
LOCATION: REMOTE I/O PANEL
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 8
QUANTITY: 4

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: PUMP HOUSE -PLC
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: SWITCH YARD
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 6
QUANTITY: 3

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: WORK SHOP BUILDING (MECH)
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: DMPLANT
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 6
QUANTITY: 3

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: WARE HOUSE
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 6
QUANTITY: 3

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: SECURITY BUILDING
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 12
QUANTITY: 6

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: ENERGYMETER ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: WINDOW
LOCATION: NOX PANEL
EACH CAPACITY: 1.5
TOTAL CAPACITY IN TR: 3
QUANTITY: 2

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: BARGE I & C ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: GAS SKID
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: MCC ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 6
QUANTITY: 3

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: 6.6 KV ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 6
QUANTITY: 3

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: O & M BUILDING SERVER ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: NAPTHA ENCLOSURES
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 8
QUANTITY: 4

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: BATTERY BANK ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: WARE HOUSE OFFICE ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: DMPLANT OFFICE ROOM
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 2
QUANTITY: 1

MAKE: VOLTAS
TYPE: SPLIT
LOCATION: WORK SHOP (ELEC & INST)
EACH CAPACITY: 2
TOTAL CAPACITY IN TR: 4
QUANTITY: 2

O & M BUILDING:
MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: GROUND FLOOR
EACH CAPACITY: 5.5
TOTAL CAPACITY IN TR: 5.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: GROUND FLOOR
EACH CAPACITY: 17
TOTAL CAPACITY IN TR: 17
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: GROUND FLOOR
EACH CAPACITY: 5.5
TOTAL CAPACITY IN TR: 5.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: GROUND FLOOR
EACH CAPACITY: 17
TOTAL CAPACITY IN TR: 17
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: GROUND FLOOR
EACH CAPACITY: 5.5
TOTAL CAPACITY IN TR: 5.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 1ST FLOOR
EACH CAPACITY: 8.5
TOTAL CAPACITY IN TR: 8.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 1ST FLOOR
EACH CAPACITY: 5.5
TOTAL CAPACITY IN TR: 5.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 1ST FLOOR
EACH CAPACITY: 8.5
TOTAL CAPACITY IN TR: 8.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 1ST FLOOR
EACH CAPACITY: 5.5
TOTAL CAPACITY IN TR: 5.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 1ST FLOOR
EACH CAPACITY: 8.5
TOTAL CAPACITY IN TR: 8.5
QUANTITY: 1

MAKE: CARRIER
TYPE: CENTRALIZED
LOCATION: 2ND FLOOR
EACH CAPACITY: 17
TOTAL CAPACITY IN TR: 17
QUANTITY: 1

OFFER 013
M. BLACK START DG SET
BLACK START DG SET IS A DIESEL ENGINE DRIVEN GENERATING UNIT. THIS IS USED FOR PLANT START UP AND AUXILIARY SUPPLY DURING GRID FAILURE LEADING TO COMPLETE PLANT BLANK OUT. THE UNIT IS CONNECTED TO 415 V CMCC 1 AND SUPPLIES POWER TO CMCC 1 AND CMCC 2 THROUGH BUS TIE. THERE IS A FACILITY TO EXTEND POWER SUPPLY TO ONSHORE 415 V MCC FOR DM PLANT, FUEL HANDLING AND PLANT LIGHTING LOAD.
RATING: 1500 KW, 415 V, 1500 RPM, 50 HZ
MANUFACTURER: MITSUBISHI
DIESEL ENGINE
MODEL: S16R – PTA
TYPE: FOUR CYCLE, WATER COOLED, TURBO CHARGED
OUTPUT: STANDBY 2131 HP
NO OF CYLINDERS: V – 16 CYLINDERS
SPEED: 1500 RPM
BORE X STROKE: 170mm X 180mm
DISPLACEMENT: 65.37 LITRE
COMPRESSION RATIO: 14.0: 1
BREAK MEAN EFFECTIVE PR: 20.2 KG/CM2
ROTATING DIRECTION: COUNTER CLOCKWISE (FLYWHEEL SIDE)

OFFER 014
N. PLANT CONTROLS AND INSTRUMENTATION
GAS TURBINE CONTROL SYSTEM
GE HAS PROVIDED MANY GAS TURBINES TO MANY CUSTOMERS WITH SIMPLEX AND REDUNDANT GAS TURBINE CONTROL SYSTEMS WHICH HAVE BEEN PRODUCED BY WOODWARD.
MICRO NET PLUS IS THE GAS TURBINE CONTROL SYSTEM WHICH WAS SUPPLIED BY GE. IT IS THE LATEST IN LONG LINE OF ELECTRONIC CONTROL SYSTEM PLATFORM USED TO PERFORM SPEED, LOAD AND PROCESS CONTROL FOR ALL TYPES OF PRIME MOVERS. THE STANDARD MICRO NET I/O MODULES ARE AVAILABLE TO BUILD UP A CUSTOM CONTROL SYSTEM FOR ANY TYPE OR ANY SIZE OF APPLICATION.
THE MICRO NET PLUS CONTROL SYSTEM IS A FLEXIBLE, STATE-OF-THE-ART DIGITAL CONTROL SYSTEM DESIGNED SPECIFICALLY FOR PRIME MOVER CONTROL APPLICATIONS SUCH AS:
GAS TURBINE CONTROL
STEAM TURBINE CONTROL
HYDRO TURBINE CONTROL
DIESEL AND GAS ENGINE CONTROL

SYSTEM FEATURES
MICRO NET CONTROL SYSTEM CONSISTS OF HARDWARE AND SOFTWARE PARTS:
HARDWARE PARTS:
CHASSIS AND SLOTS
POWER SUPPLY UNITS
MOTOROLA CPU5200 PROCESSOR
HMI (HUMAN MACHINE INTERFACE)
I/O MODULES AND FTM‟S (FIELD TERMINATION MODULES)
FIBRE-OPTIC SWITCH
RIO – REMOTE I/O PANEL
LIO – LOCAL I/O PANEL

SOFTWARE PARTS:
GAP – GRAPHICAL APPLICATION PROGRAM
WATCH WINDOWS
CODER
APPLICATION MANAGER
SERVLINK OPC SERVER
CONTROL ASSISTANT

OFFER 015
O. PLANT FIRE FIGHTING SYSTEM
THE PLANT FIRE PROTECTION SYSTEM CONSIST OF HYDRANT SYSTEM, HIGH VELOCITY WATER SPRAY SYSTEM FOR TRANSFORMERS, FIRE DETECTION AND ALARM SYSTEM, CO2 FIRE FIGHTING SYSTEM FOR RACK ROOM AND CONTROL ROOM AND PORTABLE EXTINGUISHERS. THE SYSTEM IS DESIGNED BY M/S AGNI HEAVY ENGINEERING LIMITED. ADDRESSABLE FIRE PROTECTION & DETECTION SYSTEM OF NOTIFIER IS PROVIDED FOR ENTIRE BARGE AND SEMI ADDRESSABLE FOR REMAINING PART OF THE PLANT.

EMERGENCY FIRE PUMP
MAKE: KIRLOSKAR BROTHERS LIMITED
MODEL: 6 UP4
CAPACITY: 273 M3/HR
TOTAL HEAD: 70 M WC
SHUTOFF HEAD: 72 M WC
POWER REQUIRED AT DUTY POINT: 76.57 KW
EFFICIENCY: 70%
RECOMMENDED MINIMUM FLOW: 100 M3/HR
NPSH REQUIRED: 3.5 M
TYPE OF COOLING: SELF COOLING
TYPE OF LUBRICATION: GREASE
TYPE OF PUMP: HORIZONTAL SPLIT CASING CENTRIFUGAL PUMP
NO OF STAGES: SINGLE
TYPE OF COUPLING: SPIDER COUPLING
DIRECTION OF ROTATION FROM DRIVING END: CLOCKWISE
DIESEL ENGINE
MANUFACTURER: CUMMINS INDIA LIMITED
TYPE: MECHANICAL (AIR LESS) DIRECT INJECTION
4 STROKE CYCLE AND COLD STARTING TYPE
TURBO CHARGED
MODEL: NT-495-F1
DESIGN STANDARD: BS:5514
NO OF CYLINDERS: 4
RPM: 1500
BHP AT RATED RPM: 127 BHP
ENGINE STARTING DETAILS: 24 V ELECTRICAL START
FUEL CONSUMPTION: 25 LITRE / HR
FUEL CONSUMPTION AT 150 % OF RATED: 31 LITRE / HR
TYPE OF COOLING: WATER COOLED WITH HEAT EXCHANGER
FUEL TANK CAPACITY: 200 LITRE
BATTERY: 4 X 12 V – 180 AH CAPACITY

OFFER 016
P. START UP VACUUM SYSTEM
START-UP VACUUM PUMP
MANUFACTURER: NASH KOREA
TYPE: LIQUID RING
HOGGING CAPACITY AT 10 INCH HGA: 595 SM3/HR
EVACUATION VOLUME: 450 M3
HOGGING SUCTION PRESSURE: 254mm HGA
SUCTION TEMPERATURE: 33 DEG.C
BHP: 42 KW
NO OF STAGE: 1
SPEED: 590 RPM
HOGGING TIME REQUIRED TO REDUCE SUCTION PR
FROM ATMOSPHERE PR TO 254 MM HGA: 20 MIN
DISCHARGE PR: ATMOSPHERIC
MATERIAL OF CONSTRUCTION
CASING: A48
SHAFT: KSD 3752 SM45C (EQ. A576)
ROTOR: A536
PUMP DIRECTION OF ROTATION: C.W FROM DRIVER END
NO OF BEARINGS: 2
TYPE OF BEARING: ROLLER
TYPE OF LUBRICATION: GREASE
PUMP-MOTOR COUPLING: FLEXIBLE
SEAL WATER REQUIREMENT
FLOW: 7.95 M3/HR
TEMPERATURE: 35 DEG.C

MOISTURE SEPARATOR
DIMENSION: O.D 390 MM X 1375 MM H
MATERIAL: KSD 3503 (EQ. A283)

SILENCER
SIZE: O.D 460 MM X 1830 MM H
TYPE: VERTICAL
MATERIAL: KSD 3503 (EQ. A283)

MOTOR
RATING: 45 KW
POLES: 10 POLES
ROTOR TYPE: SQUIRREL CAGE
ENCLOSURE: TOTALLY ENCLOSED
COOLING METHOD: FAN COOLED
FREQUENCY: 50 HZ
PHASE: 3
INSULATION CLASS: F
TEMPERATURE RISE AT FULL LOAD: 90 DEG.C
VOLTAGE: 415 V
NO LOAD CURRENT: 75 A
FULL LOAD CURRENT: 113 A
STARTING CURRENT: 670 A
SPEED: 590 RPM
EFFICIENCY
AT 1/2 LOAD: 85 %
AT 3/4 LOAD: 87.5 %
AT FULL LOAD: 88 %
POWER FACTOR
AT 1/2 LOAD: 54 %
AT 3/4 LOAD: 60 %
AT FULL LOAD: 63 %
QUANTITY: 1

OFFER 017
Q. STEAM TURBINE DEAERATING CONDENSER
HEAT DUTY AT RATED CONDITION: 473800000 KJ/HR
HEAT DUTY AT HP/LP BYPASS VALVE OPERATION: 669700000 KJ/HR
MAXIMUM DISSOLVED OXYGEN CONTENT: 7 PPB
CONDENSER PRESSURE: 0.077 BARA
CONDENSATE TEMPERATURE: 40.8 DEG.C
MANUFACTURER: HHI
APPLIED DESIGN CODE: HEI
OPERATING LIFE: 30 YEARS
REFERENCE CONDITION
BAROMETRIC PRESSURE: 1.004 BARA
RELATIVE HUMIDITY: 75 %
AMBIENT AIR TEMP: 31 DEG.C
COOLING WATER TEMP (SEA WATER): 29 DEG.C
MAXIMUM MAKEUP WATER: 30 M3/HR
TYPE: DEAERATING CONDENSER
HOTWELL CAPACITY
FROM NORMAL LEVEL TO LOW LEVEL: 3 MINUTES
FROM NORMAL LEVEL TO BOTTOM: 5 MINUTES
NO OF PASSES: 2

PERFORMANCE AT RATED CONDITION
LP TURBINE EXHAUST
FLOW: 225619 M3/HR
ENTHALPY: 2266.7 KJ/KG
GLAND STEAM CONDENSER DRAIN
FLOW: 245 KG/HR
ENTHALPY: 196.2 KJ/KG
STEAM JET AIR EJECTOR DRAIN
FLOW: 300 KG.HR
ENTHALPY: 193.5 KJ/KG
CONDENSATE LEAVING CONDENSER
FLOW: 226164 KG/HR
ENTHALPY: 170.8 KJ/KG
TEMPERATURE: 40.8 DEG.C
PRESSURE: 0.077 BARA
CIRCULATING WATER
INLET TEMPERATURE: 29 DEG.C
TEMPERATURE RISE: 8 DEG.C
INLET PR: 2.2 BARA
FLOW: 14565 M3/HR
SPECIFIC GRAVITY: 1.02
HEAD LOSS: 4.5 M

PERFORMANCE AT 100 %BYPASS
HP BYPASS
FLOW: 194040 KG/HR
ENTHALPY: 2770.9 KJ/KG
TEMPERATURE: 162 DEG.C
PRESSURE: 5 BARA
LP BYPASS
FLOW: 65812 KG/HR
ENTHALPY: 2745.3 KJ/KG
TEMPERATURE: 143 DEG.C
PRESSURE: 3 BARA
CONDENSER NECK SPRAY FROM CEP OUTLET
FLOW: 5983 KG/HR
ENTHALPY: 191.2 KJ/KG
CONDENSATE LEAVING CONDENSER
FLOW: 266236 KG/HR
ENTHALPY: 191.3 KJ/KG
TEMPERATURE: 45.7 DEG.C
PRESSURE: 0.0993 BARA
COOLING WATER INLET TEMP: 29 DEG.C
COOLING WATER OUTLET TEMP: 40.3 DEG.C

TUBING
DIAMETER: 25.4mm
THICKNESS MM (BWG): 0.5 (25), 0.7 (22)
EFFECTIVE SURFACE AREA: 5137 M2 (5292 M2)
NO OF TUBES: 7852 (8088)
25 BWG: 7952
22 BWG: 136
EFFECTIVE LENGTH: 8200mm
TUBE VELOCITY: 2.2 M/S
CLEANLINESS FACTOR: 0.9
WATER BOX VELOCITY (INLET): 1.964 M/S
QUANTITY: 1

QUANTITY: 1 PLANT